Plan Review Notes
Plan Review Notes For Permit 03040477
Permit Number 03040477
Review Stop B
Sequence Number 7
Notes
Date Text
2004-01-28 00:00:00TRUSS ENGINEERING PREPARED BY THOMAS
 KELAHER, PE. DATED VARIOUSLY 11/25/03
 AND 12/12/03.
  
 THE REVIEW OF DELEGATED ENGINEERING
 SHOULD BE BY THE ENGINEER OF RECORD,
 NOT AN EIT.
  
 SHEETS DATED 12/12/03 LABELED SHOP
 DRAWING SK-01 AND OTHERS LABELED RT-01,
 H-02, ETC., SIGNED AND SEALED BY T.
 KELAHER DO NOT SHOW ANY LOADING OR
 CRITERIA USED FOR THE DESIGN.
  
 THE COMPUTER CALCULATIONS PROVIDED ARE
 NOT REFERENCED OR RECOGNIZED IN THE
 KELAHER COVER LETTER.THE COVER LETTER
 "METAL STUD ROOF FRAMING
 SPECIFICATIONS" DOES NOT REFENCE OR
 INDEX ANY OF THE OTHER TRUSS DESIGN
 INFORMATION.
  
 PLEASE REVISE AS NECESSARY.