Plan Review Notes
Plan Review Notes For Permit 03040477
Permit Number 03040477
Review Stop B
Sequence Number 4
Notes
Date Text
2003-08-01 00:00:00STH LETTER DATED 7/31/03 RE: FILLED
 MASONRY.
  
 THE ARCHITECT CITES FBC 709.3.2 AS A
 METHOD FOR CODE COMPLIANCE.THIS IS
 NOT VALID FOR THE CORE FILL 500 SINCE
 THE TEST STANDARDS ARE FOR MINERAL TYPE
 AGGREGATES AND THE FOAM BASED MATERIAL
 DOES NOT LEND ITSELF TO THOSE METHODS.
  
 BASED ON THE INFORMAION PROVIDED,
 PARTICULARLY THE SOUTHWEST RESEARCH
 INSTITUTE, DATA, IT MAY BE APPROVED FOR
 USE UNDER FBC 103.7 ALTERNATE MATERIALS
 AND METHODS.
  
 THERE ARE SOME CONFLICTS IN THE
 INFORMATION THAT MUST BE RESOLVED
 BEFORE THE BUILDING OFFICIAL MAY RENDER
 A DECISION TO ACCEPT THIS MATERIAL/METHO
  
 PAGE 30F5 IN REPORT 01-6740-711 DATED
 8/95 STATED THAT TEST ASSEMBLY HAD
 CELLS FILLED WITH MORTAR AS SHOWN IN
 FIGURE A-3 OF APPENDIX A.THIS APPENDIX
 AND FIGURE ARE NOT INCLUDED AND APPEAR
 TO BE A KEY ELEMENT IN THE TEST WHEN
 TAKEN IN THE CONTEXT OF THE
 INTRODUCTION TO THE REPORT.
  
 THE SWRI LETTER TO JACK TEMPLE DATED
 11/4/96 REFERENCES AN SWRI FINAL REPORT
 01-7522-607 WHICH IS DIFFERENT THAN THE
 01-6740-711 PROVIDED.
  
 PLEASE REVIEW FBC 103.7 AND PROVIDE
 COMPLETE AND COMPLEMENTARY DATA SO THAT
 EQUIVALENT CODE COMPLIANCE MAY BE
 DETERMINED.