| 2003-08-01 00:00:00 | STH LETTER DATED 7/31/03 RE: FILLED |
| | MASONRY. |
| | |
| | THE ARCHITECT CITES FBC 709.3.2 AS A |
| | METHOD FOR CODE COMPLIANCE.THIS IS |
| | NOT VALID FOR THE CORE FILL 500 SINCE |
| | THE TEST STANDARDS ARE FOR MINERAL TYPE |
| | AGGREGATES AND THE FOAM BASED MATERIAL |
| | DOES NOT LEND ITSELF TO THOSE METHODS. |
| | |
| | BASED ON THE INFORMAION PROVIDED, |
| | PARTICULARLY THE SOUTHWEST RESEARCH |
| | INSTITUTE, DATA, IT MAY BE APPROVED FOR |
| | USE UNDER FBC 103.7 ALTERNATE MATERIALS |
| | AND METHODS. |
| | |
| | THERE ARE SOME CONFLICTS IN THE |
| | INFORMATION THAT MUST BE RESOLVED |
| | BEFORE THE BUILDING OFFICIAL MAY RENDER |
| | A DECISION TO ACCEPT THIS MATERIAL/METHO |
| | |
| | PAGE 30F5 IN REPORT 01-6740-711 DATED |
| | 8/95 STATED THAT TEST ASSEMBLY HAD |
| | CELLS FILLED WITH MORTAR AS SHOWN IN |
| | FIGURE A-3 OF APPENDIX A.THIS APPENDIX |
| | AND FIGURE ARE NOT INCLUDED AND APPEAR |
| | TO BE A KEY ELEMENT IN THE TEST WHEN |
| | TAKEN IN THE CONTEXT OF THE |
| | INTRODUCTION TO THE REPORT. |
| | |
| | THE SWRI LETTER TO JACK TEMPLE DATED |
| | 11/4/96 REFERENCES AN SWRI FINAL REPORT |
| | 01-7522-607 WHICH IS DIFFERENT THAN THE |
| | 01-6740-711 PROVIDED. |
| | |
| | PLEASE REVIEW FBC 103.7 AND PROVIDE |
| | COMPLETE AND COMPLEMENTARY DATA SO THAT |
| | EQUIVALENT CODE COMPLIANCE MAY BE |
| | DETERMINED. |