| 2003-07-16 00:00:00 | THE STH LETTER DATED 6/24/03 RESPONDED |
| | TO THE REQUEST FOR INFORMATION AND/OR |
| | CODE DEFICIENCIES CONTAINED IN THE |
| | 5/28/03 COMMENT LIST. |
| | |
| | THE THRESHOLD INSPECTION PLAN HAS BEEN |
| | RECEIVED, HOWEVER THE STATEMENT |
| | REQUIRED BY FS 553 TO APPEAR ON THE |
| | PLANS HAS NOT.THE ARCHITECT'S |
| | RESPONSE TO SEE THE ENCLOSED LETTER |
| | FROM ONMJ IS NOT SUFFICIENT, NOR WAS AN |
| | LETTER FOUND.PLEASE REVISE THE PLANS |
| | AS NECESSARY. |
| | |
| | THE REQUEST FOR THE LISTING OF THE |
| | RINKER T-14 BLOCK MEETING A THREE HOUR |
| | RATING WAS RESPONDED TO WITH A UL |
| | LISTING U905. RINKER WAS NOT FOUND AS |
| | AN "ELIGIBLE MANUFACTURER" AS CALLED FOR |
| | IN ITEM #1 OF THAT LISTING.PLEASE |
| | PROVIDE DATA DEMONSTRATING COMPLIANCE |
| | WITH FBC 701.5. |
| | |
| | THE HUSTON SEATING PLAN DATED 6/13/03 |
| | DOES NOT APPEAR TO HAVE THE 19" CLEAR |
| | SPACE BETWEEN THE CHAIR AND TABLE IN |
| | ACCORDANCE WITH FBC 1019.10.3.5.1 FOR |
| | LECTURE ROOMS 1, 2 AND 3. |
| | |
| | THE EMERGENCY LIGHING REQUIRED BY FBC |
| | 1016.2 IS NOT SHOWN ON THE PLANS.A |
| | SEPARATE RESPONSE BY THE ELECTRICAL |
| | ENGINEER AS NOTED IN THE ARCHITECT'S |
| | RESPONSE, HAS NOT BEEN FOUND.PLEASE |
| | REVISE AS NECESSARY. |
| | |
| | PANIC HARDWARE IS REQUIRED IN |
| | CLASSROOMS 1, 2 AND 3 AS DEPICTED ON |
| | SHEET A1.3.2 SINCE THE OCCUPANT LOAD IS |
| | > 100.SEE FBC 1021.3.1. |