Plan Review Notes
Plan Review Notes For Permit 03040477
Permit Number 03040477
Review Stop B
Sequence Number 3
Notes
Date Text
2003-07-16 00:00:00THE STH LETTER DATED 6/24/03 RESPONDED
 TO THE REQUEST FOR INFORMATION AND/OR
 CODE DEFICIENCIES CONTAINED IN THE
 5/28/03 COMMENT LIST.
  
 THE THRESHOLD INSPECTION PLAN HAS BEEN
 RECEIVED, HOWEVER THE STATEMENT
 REQUIRED BY FS 553 TO APPEAR ON THE
 PLANS HAS NOT.THE ARCHITECT'S
 RESPONSE TO SEE THE ENCLOSED LETTER
 FROM ONMJ IS NOT SUFFICIENT, NOR WAS AN
 LETTER FOUND.PLEASE REVISE THE PLANS
 AS NECESSARY.
  
 THE REQUEST FOR THE LISTING OF THE
 RINKER T-14 BLOCK MEETING A THREE HOUR
 RATING WAS RESPONDED TO WITH A UL
 LISTING U905. RINKER WAS NOT FOUND AS
 AN "ELIGIBLE MANUFACTURER" AS CALLED FOR
 IN ITEM #1 OF THAT LISTING.PLEASE
 PROVIDE DATA DEMONSTRATING COMPLIANCE
 WITH FBC 701.5.
  
 THE HUSTON SEATING PLAN DATED 6/13/03
 DOES NOT APPEAR TO HAVE THE 19" CLEAR
 SPACE BETWEEN THE CHAIR AND TABLE IN
 ACCORDANCE WITH FBC 1019.10.3.5.1 FOR
 LECTURE ROOMS 1, 2 AND 3.
  
 THE EMERGENCY LIGHING REQUIRED BY FBC
 1016.2 IS NOT SHOWN ON THE PLANS.A
 SEPARATE RESPONSE BY THE ELECTRICAL
 ENGINEER AS NOTED IN THE ARCHITECT'S
 RESPONSE, HAS NOT BEEN FOUND.PLEASE
 REVISE AS NECESSARY.
  
 PANIC HARDWARE IS REQUIRED IN
 CLASSROOMS 1, 2 AND 3 AS DEPICTED ON
 SHEET A1.3.2 SINCE THE OCCUPANT LOAD IS
 > 100.SEE FBC 1021.3.1.