| Plan Review Notes For Permit 03040477 |
| Permit Number |
03040477 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-23 00:00:00 | DENIED: | | | | | | THE FOLLOWING ITEMS NOT ADDRESSED FROM | | | PREVIOUS REVIEW DATED 4-30-03. | | | ITEM # | | | 2.PLAN SHEET AC-2 STORAGE RM 117, | | | EXHAUST TERMINATES OVER THE DOOR.2001 | | | FBC(M) 401.5.2 EXHAUST SHALL NOT BE | | | DIRECTED ONTO WALKWAYS.FRESH AIR | | | INTAKE SHALL BE A MINIMUM OF 10 FT FROM | | | EXHAUST AS PER 2001 FBC(M) 401.5.1. | | | ITEM # | | | 3. PLAN SHEET AC-7 WAS REVISED TO SHOW | | | RESTROOM EXHAUST RISER IN A RATED SHAFT. | | | DUCTWORK FROM HOOD THAT ALSO PENTRATES | | | THROUGH MORE THAN ONE FLOOR SHALL ALSO | | | BE IN FIRE RATED SHAFT. 2001 FBC(M) | | | 607.4. SEE ALSO 510.6.1. | | | ITEM # | | | 5.PLEASE REFER TO 2001 FBC(M) 510 FOR | | | HAZARDOUS EXHAUST SYSTEMS CONCERNING THE | | | THE FUME HOODS EXHAUST AND MAKE-UP AIR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|