| Plan Review Notes For Permit 03040477 |
| Permit Number |
03040477 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-06-13 00:00:00 | 1) COULD NOT LOCATE INTERIOR FINISH | | | CLASSIFCATION FOR WALLS AND CEILINGS. | | | | | | 2) NOTE ON DOOR SCHEDULE STILL INDICATES | | | UNDERCUTTING FIRE RATED DOORS. PLEASE | | | EXPLAIN. | | | | | | 3) WHY IS THE EXHAUST DUCT FOR HOOD 1 | | | AND HOOD 2 NOT ENCLOSED IN A RATED | | | SHAFT. | | | | | | 4) WHERE IS THE FDC. PLEASE SHOW ITS | | | RELATIONSHIP TO A FIRE HYDRANT WITHIN | | | 150 FEET. | | | | | | 5) NO EXIT SIGNS SHOWN ON ELECTRICAL | | | DRAWINGS NEAR LECTURE HALL DOORS | | | WITHIN PARTITIONS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|