Plan Review Notes
Plan Review Notes For Permit 03040477
Permit Number 03040477
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2003-06-13 00:00:001) COULD NOT LOCATE INTERIOR FINISH
 CLASSIFCATION FOR WALLS AND CEILINGS.
  
 2) NOTE ON DOOR SCHEDULE STILL INDICATES
 UNDERCUTTING FIRE RATED DOORS. PLEASE
 EXPLAIN.
  
 3) WHY IS THE EXHAUST DUCT FOR HOOD 1
 AND HOOD 2 NOT ENCLOSED IN A RATED
 SHAFT.
  
 4) WHERE IS THE FDC. PLEASE SHOW ITS
 RELATIONSHIP TO A FIRE HYDRANT WITHIN
 150 FEET.
  
 5) NO EXIT SIGNS SHOWN ON ELECTRICAL
 DRAWINGS NEAR LECTURE HALL DOORS
 WITHIN PARTITIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910