| Plan Review Notes For Permit 03040477 |
| Permit Number |
03040477 |
|
| Review Stop |
ENG |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-15 00:00:00 | FAILED: | | | 1. PLEASE NOTE THAT A SEPARATE PERMIT | | | APPLICATION AND FEES FOR UNDERGROUND | | | UTILITIES AND SITE WORK WILL BE REQUIRED | | | 2. A SEPARATE BACKFLOW PREVENTER IN | | | 2 1/2" WATER SERVICE TO THE BUILDING IS | | | REQUIRED. | | | 3. IS THERE ANY EXSITING DDCV ON 8" FIRE | | | LINE ON SITE?, IF SO PLEASE SHOW. | | | 4. BROKEN/ DAMAGED SIDEWALK, CURB & | | | GUTTERS AT ALL SIDE OF PROPERTY MUST BE | | | RESTORED/REPALCED. | | | 5. CIVIL /SITE PLANS MUST BE APPROVED | | | BY PUBLIC UTILITIES PRIOR TO ISSUANCE OF | | | CIVIL/SITE PERMIT BY BUILDING DEPARTMENT | | | 6. ANY CONSTRUCTION IN DIXIE HWY WILL | | | REQUIRE A SEPARATE PERMIT FROM FDOT. | | | 7. PLEASE PROVIDE EASEMENT FOR FOOTING, | | | AREAL ENCROACHMENT INTO THE PUBLIC ROW | | | TO PUBLIC UTILITIES, ATT: VINCE NOEL, | | | 659-8040 EXT. 8440 | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|