| Plan Review Notes For Permit 03040477 |
| Permit Number |
03040477 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-19 00:00:00 | ************** UNSAT ********** | | | | | | 1)NOTE: PLEASE CLARIFY CONTROL VOLTAGE | | | OF CHILLER PLANT CONTROL WIRING? | | | PLEASE CLARIFY MEANS OF DISC IN MAIN | | | ELECTRICAL ROOM FOR ALL CONTROL WIRING | | | FEEDING ANOTHER BLDG FROM A SEPARATE | | | SERVICE? 225-31 | | | ALL DISC SHALL HAVE SIGNAGE AS REQ`D PER | | | NEC. 230-2 | | | | | | 2)NOTE: PLEASE SEE 384-16 FOR MAIN | | | REQ`D ON SECONDARY SIDE OF TRANSFORMER | | | FOR PANEL "4LA". | | | | | | 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. 230-42,215-3 ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|