Plan Review Notes
Plan Review Notes For Permit 03040477
Permit Number 03040477
Review Stop E
Sequence Number 2
Notes
Date Text
2003-05-19 00:00:00************** UNSAT **********
  
 1)NOTE: PLEASE CLARIFY CONTROL VOLTAGE
 OF CHILLER PLANT CONTROL WIRING?
 PLEASE CLARIFY MEANS OF DISC IN MAIN
 ELECTRICAL ROOM FOR ALL CONTROL WIRING
 FEEDING ANOTHER BLDG FROM A SEPARATE
 SERVICE? 225-31
 ALL DISC SHALL HAVE SIGNAGE AS REQ`D PER
 NEC. 230-2
  
 2)NOTE: PLEASE SEE 384-16 FOR MAIN
 REQ`D ON SECONDARY SIDE OF TRANSFORMER
 FOR PANEL "4LA".
  
 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 230-42,215-3 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW