Plan Review Notes
Plan Review Notes For Permit 03040477
Permit Number 03040477
Review Stop B
Sequence Number 2
Notes
Date Text
2003-05-28 00:00:00PLANS DATED 5/3/03 NO REVISION DATE.
  
 PLEASE PROVIDE A RECENT PROPERTY SURVEY.
  
 THIS IS A THRESHOLD BUILDING AS DEFINED
 IN 553.71, FLORIDA STATUTES AND REQUIRES
 A THRESHOLD INSPECTION PLAN AND THE
 STATEMENT ON THE PLANS DECLARING
 COMPLIANCE WITH 553.
  
 PLEASE PROVIDE A LISTING OR
 SPECIFICATION THAT A RINKER T-14 BLOCK
 MEETS A THREE HOUR FIRE RATING WITH AN
 EQUIVALENT THICKNESS REQUIRED BY FBC
 709.3.
  
 SHEET A1.3.1, NOTE #1 ERRONEOUSLY
 DECLARES "UNLIMITED, UNPROTECTED
 OPENINGS FOR WALLS MORE THAN 15' ..."
 SEE FBC TABLE 600, FBC 705 SPEAKS TO
 FIRE PROTECTION OF OPENINGS, NOT AREA.
 PLEASE REVISE AS NECESSARY.
  
 SHEETS A1.3.1 AND 1.3.2.SHOW A
 SEATING PLAN AND AISLE WIDTHS.SEE FBC
 1003.1.2.
  
 SHEET A1.3.3, ROOM 307.THE
 MEASUREMENTOF THE DIAGONAL DISTANCE
 SEPARATION OF THE EXIT ACCESS DOORS IS
 INCORRECT AS SHOWN ON THE PLAN.A
 STRAIGHT LINE DISTANCE IS USED. SEE FBC
 1004.1.4 AND REVISE AS NECESSARY.
  
 SHEET A1.4.1 INCORRECTLY CALCULATES THE
 RATIO OF WALL OPENINGS TO WALL AREA.
 THE WALL AREA FOR TABLE 600 IS BASED ON
 A PER FLOOR AREA, AND AS MEASURED FROM
 FLOOR TO CEILING NEXT ABOVE.OPENINGS
 ARE TAKEN AS THE ROUGH OPENING SIZE.
 PLEASE REVISE AS NECESSARY.
  
 WHAT IS THE GATE AND HAND RAIL SHOWN IN
 SECTION 1 SHEET A5.2.1 USED FOR?
  
 SHEET A5.2.2 THE DELEGATION OF THE
 DESIGN OF THE STAIRS REQUIRES SPECIFIC
 INFORMATION NOT A CODE SECTION
 REFERENCE.SEE FBC 104.2.
  
 SHEET A6.1.1 HAS REFERENCE TO A GLAZING
 SCHEDULE AND SPECIFICATIONS NOT PROVIDED
 WITH THIS PERMIT APPLICATION.
  
 SHEET A6.2.1 SHOWS A SCREEN IN THE IN
 THE EMERGENCY OVERFLOW SCUPPER PIPE.
 WHATVOLUME OF WATER IS CALCULATED TO
 FLOW THROUGH THIS SCREEN AT WHAT RATES?
 SEE FBC 1503.4.
  
 SHEET A6.2.2, SECTION 6.SHOW A
 CONSTRUCTION DETAIL FOR THE SUSPENDED
 PLASTER SOFIT INCLUDING FRAMING AND
 FASTENERS. SEE FBC 104.2.
  
 SHEET A7.2.1 CALLS FOR THE UNDERCUTTING
 OF FIRE RATED DOORS.SEE NFPA 80 FOR
 LIMITATIONS.
  
 SHEET S1 SHOWS COLUMN FOOTINGS EXTENDING
 BEYOND THE APPARENT PROPERTY LINE.
 SEE FBC 3207.
  
 SHEET S6 CITES SSTD 12-97.SSTD 12-99
 IS INVOKED BY THE FBC, PLEASE REVISE
 AND INSURE COMPLIANCE AS NECESSARY.
  
 SHEET S4, SHOW THE METHOD OF FIRE
 PROTECTION FOR THE COLUMNS SHOWN AS SC2.
 AND THE STEEL COLUMNS SHOWN IN SECTION
 3/6.1.2.
  
 SHEET S7, SHOW THE FIRE PROTECION FOR
 THE STRUCTURE SHOWN IN SECTION AS
 TYPICAL HANGING PARTITION DETAIL.
  
 SHOW HOW COMPLIANCE WITH FBC 1405 WILL
 BE ACCOMPLISHED, (FIRE DEPARTMENT
 ACCESS), WITH REGARDS TO THE HURRICANE
 MISSILE IMPACT GLAZING.SEE FBC 903.5
 #2 FOR PERSPECTIVE.
  
 SHOW THE PANIC HARDWARE FOR THE DOORS IN
 ACCORDANCE WITH FBC 1021.3.1.
  
 SHOW THE STAIR IDENTIFICATION AS
 PROVIDED FOR IN FBC 1016.4.
  
 SHOW THE EMERGENCY LIGHTING FOR THE
 COVERED WALKWAYS ON THE SOUTH AND WEST
 SIDES OF THE FIRST FLOOR. SEE FBC 1016.2
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFIEC AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.