| 2003-05-28 00:00:00 | PLANS DATED 5/3/03 NO REVISION DATE. |
| | |
| | PLEASE PROVIDE A RECENT PROPERTY SURVEY. |
| | |
| | THIS IS A THRESHOLD BUILDING AS DEFINED |
| | IN 553.71, FLORIDA STATUTES AND REQUIRES |
| | A THRESHOLD INSPECTION PLAN AND THE |
| | STATEMENT ON THE PLANS DECLARING |
| | COMPLIANCE WITH 553. |
| | |
| | PLEASE PROVIDE A LISTING OR |
| | SPECIFICATION THAT A RINKER T-14 BLOCK |
| | MEETS A THREE HOUR FIRE RATING WITH AN |
| | EQUIVALENT THICKNESS REQUIRED BY FBC |
| | 709.3. |
| | |
| | SHEET A1.3.1, NOTE #1 ERRONEOUSLY |
| | DECLARES "UNLIMITED, UNPROTECTED |
| | OPENINGS FOR WALLS MORE THAN 15' ..." |
| | SEE FBC TABLE 600, FBC 705 SPEAKS TO |
| | FIRE PROTECTION OF OPENINGS, NOT AREA. |
| | PLEASE REVISE AS NECESSARY. |
| | |
| | SHEETS A1.3.1 AND 1.3.2.SHOW A |
| | SEATING PLAN AND AISLE WIDTHS.SEE FBC |
| | 1003.1.2. |
| | |
| | SHEET A1.3.3, ROOM 307.THE |
| | MEASUREMENTOF THE DIAGONAL DISTANCE |
| | SEPARATION OF THE EXIT ACCESS DOORS IS |
| | INCORRECT AS SHOWN ON THE PLAN.A |
| | STRAIGHT LINE DISTANCE IS USED. SEE FBC |
| | 1004.1.4 AND REVISE AS NECESSARY. |
| | |
| | SHEET A1.4.1 INCORRECTLY CALCULATES THE |
| | RATIO OF WALL OPENINGS TO WALL AREA. |
| | THE WALL AREA FOR TABLE 600 IS BASED ON |
| | A PER FLOOR AREA, AND AS MEASURED FROM |
| | FLOOR TO CEILING NEXT ABOVE.OPENINGS |
| | ARE TAKEN AS THE ROUGH OPENING SIZE. |
| | PLEASE REVISE AS NECESSARY. |
| | |
| | WHAT IS THE GATE AND HAND RAIL SHOWN IN |
| | SECTION 1 SHEET A5.2.1 USED FOR? |
| | |
| | SHEET A5.2.2 THE DELEGATION OF THE |
| | DESIGN OF THE STAIRS REQUIRES SPECIFIC |
| | INFORMATION NOT A CODE SECTION |
| | REFERENCE.SEE FBC 104.2. |
| | |
| | SHEET A6.1.1 HAS REFERENCE TO A GLAZING |
| | SCHEDULE AND SPECIFICATIONS NOT PROVIDED |
| | WITH THIS PERMIT APPLICATION. |
| | |
| | SHEET A6.2.1 SHOWS A SCREEN IN THE IN |
| | THE EMERGENCY OVERFLOW SCUPPER PIPE. |
| | WHATVOLUME OF WATER IS CALCULATED TO |
| | FLOW THROUGH THIS SCREEN AT WHAT RATES? |
| | SEE FBC 1503.4. |
| | |
| | SHEET A6.2.2, SECTION 6.SHOW A |
| | CONSTRUCTION DETAIL FOR THE SUSPENDED |
| | PLASTER SOFIT INCLUDING FRAMING AND |
| | FASTENERS. SEE FBC 104.2. |
| | |
| | SHEET A7.2.1 CALLS FOR THE UNDERCUTTING |
| | OF FIRE RATED DOORS.SEE NFPA 80 FOR |
| | LIMITATIONS. |
| | |
| | SHEET S1 SHOWS COLUMN FOOTINGS EXTENDING |
| | BEYOND THE APPARENT PROPERTY LINE. |
| | SEE FBC 3207. |
| | |
| | SHEET S6 CITES SSTD 12-97.SSTD 12-99 |
| | IS INVOKED BY THE FBC, PLEASE REVISE |
| | AND INSURE COMPLIANCE AS NECESSARY. |
| | |
| | SHEET S4, SHOW THE METHOD OF FIRE |
| | PROTECTION FOR THE COLUMNS SHOWN AS SC2. |
| | AND THE STEEL COLUMNS SHOWN IN SECTION |
| | 3/6.1.2. |
| | |
| | SHEET S7, SHOW THE FIRE PROTECION FOR |
| | THE STRUCTURE SHOWN IN SECTION AS |
| | TYPICAL HANGING PARTITION DETAIL. |
| | |
| | SHOW HOW COMPLIANCE WITH FBC 1405 WILL |
| | BE ACCOMPLISHED, (FIRE DEPARTMENT |
| | ACCESS), WITH REGARDS TO THE HURRICANE |
| | MISSILE IMPACT GLAZING.SEE FBC 903.5 |
| | #2 FOR PERSPECTIVE. |
| | |
| | SHOW THE PANIC HARDWARE FOR THE DOORS IN |
| | ACCORDANCE WITH FBC 1021.3.1. |
| | |
| | SHOW THE STAIR IDENTIFICATION AS |
| | PROVIDED FOR IN FBC 1016.4. |
| | |
| | SHOW THE EMERGENCY LIGHTING FOR THE |
| | COVERED WALKWAYS ON THE SOUTH AND WEST |
| | SIDES OF THE FIRST FLOOR. SEE FBC 1016.2 |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED IMPACT FEES MUST BE PAID TO THE |
| | COUNTY, THE PERMIT PLANS STAMPED BY |
| | THAT OFFIEC AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.CALL 561-233-5025 FOR |
| | MORE INFORMATION. |