| Date |
Text |
| 2003-04-14 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHTS A2.1.1, A2.2.1, A2.3.1, & A2.4.1 |
| | PLEASE PROVIDE CALCULATIONS FOR MINIMUM |
| | FACILITIES PER BLDG CODE TABLE 1003.1 & |
| | PLUMBING CODE TABLE 403.1. |
| | 2) SHTS A2.2.1 & A4.2.1, STUDENT LOUNGE |
| | ROOM #206 SHALL COMPLY WITH SEC. 11-4.24 |
| | DETAIL #1, PLEASE SHOW COMPLIANCE WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | 3) PLEASE SUBMIT RISER DIAGRAMS FOR DWV, |
| | STORM, ACID WASTE, AND WATER. PLEASE |
| | SHOW ALL PIPE SIZES, TYPE OF MATERIAL. |
| | SHOW DFU'S AS THEY ACCUMULATE IN SANIT- |
| | ARY SYSTEM. SHOW SQUARE FEET AS THEY |
| | ACCUMULATE IN THE STORM SYSTEM. SHOW |
| | WATER HAMMER ARRESTORS REQUIRED IN SEC. |
| | 604.9 LOCATED NEAR THE FIXTURES IN AN |
| | "EFFECTIVE RANGE" NOT AT THE TOP OF THE |
| | DROPS IN THE CEILING. PDI-WH 201, AND |
| | MANUF. INSTALLATION INSTRUCTIONS. |
| | 4) SHT A2.2.1 PLEASE PROVIDE MANUF. INFO |
| | FOR DISTILLED WATER SYSTEM. |
| | 5) SHTS A2.3.1, A2.4.1, A4.2.1 DETAIL |
| | #5, SINKS SHALL COMPLY WITH 11-4.24 AND |
| | ALL SUBSECTIONS. PLEASE SHOW ON DETAIL |
| | AND SUBMIT DETAIL FOR FACULITY LOUNGE ON |
| | 4TH FLOOR. |
| | 6) SHT A4.1.1 DETAIL #1, PLEASE SHOW |
| | CLEAR FLOOR SPACE FOR ALL HDCP FIXTURES. |
| | SHOW 5' TURNING CIRCLE FOR TOILET ROOMS. |
| | 7) SHT A4.1.1 HDCP DETAILS, W/C TO BE |
| | 18" OFF WALL TO CENTER OF FIXTURE. SHOW |
| | ON DETAIL. - NOTE #12 DRAIN TO BE INSUL- |
| | ATED ALSO. |
| | 8) SHT P0.1 WATER HEATER DETAIL #4, |
| | THERMAL EXPANSION CONTROL REQUIRED. SEC. |
| | 607.3.2- DIELECTRIC UNIONS NOT APPROV- |
| | ED FOR USE IN WATER SYSTEM. PLEASE DE- |
| | LETE REFERENCE. |
| | 9) SHT PO.1 DILUTION TANK FOR ACID WASTE |
| | SYSTEM SHALL BE SIZED BY RODNEY COMPO, |
| | ENVIRONMENTAL COMPLIANCE. (561) 837-4074 |
| | WASTE ORD: 2938-96 |
| | 10) SHT P0.1 DETAIL #1, CONDENSATE TRAP, |
| | VENT LINE WITH PERFORATED CAP SHALL NOT |
| | TERMINATE IN A/C ROOM IF ROOM IS USED AS |
| | A PLENUM. VENT THRU ROOF REQUIRED. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |