2003-04-30 00:00:00DENIED:
  
 1.AS PER F.S. 471.025, ALL DRAWINGS,
 SPECIFICATION AND PLANS SHALL BE HAVE
 AN IMPRESSION-TYPE SEAL AND BE SIGNED,
 SEALED, AND DATED.
  
 2.PLAN SHEET AC-2 STORAGE RM 117,
 EXHAUST TERMINATES OVER THE DOOR.2001
 FBC(M) 401.5.2 EXHAUST SHALL NOT BE
 DIRECTED ONTO WALKWAYS.FRESH AIR
 INTAKE SHALL BE A MINIMUM OF 10 FT FROM
 EXHAUST AS PER 2001 FBC(M) 401.5.1.
  
 3.PLAN SHEET AC-7 DETAIL FOR THE
 RESTROOM EXHAUST RISER, AS PER 2001
 FBC(M) 607.4, DUCTS EXTENDING THROUGH
 MORE THAN ONE FLOOR SHALL BE PROTECTED
 BY A SHAFT ENCLOSURE.BUILDINGS LESS
 THAN 4 STORIES IN HEIGHT, ENCLOSURE
 SHALL HAVE A FIRE RESISTANCE RATING OF
 NOT LESS THAN 1 HR.BUILDINGS GREATER
 THAN 4 STORIES IN HEIGHT, ENCLOSURE
 SHALL BE NOT LESS THAN 2 HR RATING.
 THE ABOVE SHALL BE FOR ALL DUCTS
 PENETRATING MORE THAN ONE FLOOR.
  
 4.PLEASE CLARIFY MAKE-UP AIR FOR THE
 FUME HOODS.AIR BALANCE SCHEDULE
 INDICATES "N/A".MANUFACTURERS SPECS
 IN THE ACCESSORIES SHOWS A AUXILLARY
 AIR PLENUM KIT.WILL THIS BE UTILIZED?
  
 5.PLEASE REFER TO 2001 FBC(M) 510 FOR
 HAZARDOUS EXHAUST SYSTEMS CONCERNING THE
 FUME HOODS EXHAUST AND MAKE-UP AIR.
  
 6.PLEASE PROVIDE ENERGY CALCS.
  
 7.NO COMBUSTIBLES ABOVE THE CEILING IN
 THE RETURN AIR PLENUM. 2001 FBC(M)
 602.2.1.
  
 8.SEE PLUMBING COMMENT #10 ON
 CONDENSATE.
  
 9.SEE FIRE DEPARMENT COMMENT #22 DUCT
 SMOKE DETECTORS.
  