| Plan Review Notes For Permit 03040477 |
| Permit Number |
03040477 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-23 00:00:00 | PAID PLAN REVIEW NOT A PERMIT | | | APPLICATION. | | | | | | THE PLANS PROVIDED WERE INCOMPLETE AND | | | WITHOUT SPECIFICATIONS SO A CLOSE AND | | | CRITICAL PLAN REVIEW WAS NOT POSSIBLE. | | | | | | AT TIME OF PERMIT APPLICATION ADHERENCE | | | TO THE ITEMS IN FBC 104.3.1.1 WILL | | | ENSURE AN EXPEDITIOUS PLAN REVUE. | | | | | | THE PROPOSED BUILDING WILL BE A | | | THRESHOLD BUILDING AND MUST COMPLY WITH | | | FBC 105.13. | | | | | | SHEET A2.5.1, ROOF PLAN.THE AREA | | | DECLARED AS "UOCCUPIED SPACE" WILL BE | | | COUNTED AS A STORY SINCE IT DOES NOT | | | COMPLY WITH FBC 1511.1.1.3, FURTHER THE | | | TOTAL AREA OF ROOF STRUCTURES EXCEEDS | | | THE 1/3 ALLOTTED BY FBC 1511.1.1.2. | | | (THIS INCLUDES THE MANSARD LIKE | | | STRUCTURES) | | | | | | CONSEQUENTLY, THE PROPOSED BUILDING | | | WILL EXCEED THE ALLOWABLE HEIGHT OF 65' | | | IN TABLE 500 FOR TYPE IV 1 HOUR | | | PROTECTED CONSTRUTION. PLEASE REVISE AS | | | NECESSARY PRIOR TO PERMIT APPLICATION. | | | | | | SHEET S6 THE MASONRY COLUMN SCHEDULE | | | INDICATES 6 #7'S IN AN 8X16 BLOCK. | | | WHAT IS THE ANTICIPATED CLEAR CELL | | | SPACE FOR GROUT? |
|