Plan Review Notes
Plan Review Notes For Permit 03040477
Permit Number 03040477
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-23 00:00:00PAID PLAN REVIEW NOT A PERMIT
 APPLICATION.
  
 THE PLANS PROVIDED WERE INCOMPLETE AND
 WITHOUT SPECIFICATIONS SO A CLOSE AND
 CRITICAL PLAN REVIEW WAS NOT POSSIBLE.
  
 AT TIME OF PERMIT APPLICATION ADHERENCE
 TO THE ITEMS IN FBC 104.3.1.1 WILL
 ENSURE AN EXPEDITIOUS PLAN REVUE.
  
 THE PROPOSED BUILDING WILL BE A
 THRESHOLD BUILDING AND MUST COMPLY WITH
 FBC 105.13.
  
 SHEET A2.5.1, ROOF PLAN.THE AREA
 DECLARED AS "UOCCUPIED SPACE" WILL BE
 COUNTED AS A STORY SINCE IT DOES NOT
 COMPLY WITH FBC 1511.1.1.3, FURTHER THE
 TOTAL AREA OF ROOF STRUCTURES EXCEEDS
 THE 1/3 ALLOTTED BY FBC 1511.1.1.2.
 (THIS INCLUDES THE MANSARD LIKE
 STRUCTURES)
  
 CONSEQUENTLY, THE PROPOSED BUILDING
 WILL EXCEED THE ALLOWABLE HEIGHT OF 65'
 IN TABLE 500 FOR TYPE IV 1 HOUR
 PROTECTED CONSTRUTION. PLEASE REVISE AS
 NECESSARY PRIOR TO PERMIT APPLICATION.
  
 SHEET S6 THE MASONRY COLUMN SCHEDULE
 INDICATES 6 #7'S IN AN 8X16 BLOCK.
 WHAT IS THE ANTICIPATED CLEAR CELL
 SPACE FOR GROUT?