| Plan Review Notes For Permit 03040476 |
| Permit Number |
03040476 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) A DRINKING FOUNTAIN IS REQUIRED AND | | | A SERVICE SINK IS REQUIRED PER TABLE | | | 403.1. (ALSO SEE SECTION 410.1) | | | 2) PLUMBING RISER SHOWS THREE SINKS, BUT | | | FLOOR PLAN SHOW TWO SINKS. PLEASE | | | CLAIRFY. | | | 3) PLEASE SUBMIT A WATER RISER DIAGRAM. | | | 4) RPZ BACKFLOW REQUIRED ON WATER SERV. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|