Plan Review Notes
Plan Review Notes For Permit 03040476
Permit Number 03040476
Review Stop P
Sequence Number 1
Notes
Date Text
2003-04-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) A DRINKING FOUNTAIN IS REQUIRED AND
 A SERVICE SINK IS REQUIRED PER TABLE
 403.1. (ALSO SEE SECTION 410.1)
 2) PLUMBING RISER SHOWS THREE SINKS, BUT
 FLOOR PLAN SHOW TWO SINKS. PLEASE
 CLAIRFY.
 3) PLEASE SUBMIT A WATER RISER DIAGRAM.
 4) RPZ BACKFLOW REQUIRED ON WATER SERV.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692