| 2003-04-15 00:00:00 | ************** UNSAT ******** |
| | |
| | 1)NOTE: PLEASE SEE 250-24/ AN EQUIPMENT |
| | GROUNDING CONDUCTOR IS SHOWN ON RISER |
| | AND FROM METER TO MAIN BRK PANEL. |
| | AN EQUIPMENT GRND IS ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | |
| | 2)NOTE: PLEASE SEE 600-5 FOR MISSING |
| | REQ`D SIGN CIRCUIT. |
| | |
| | 3)NOTE: PLEASE SEE 210-62 FOR MISSING |
| | SHOW WINDOW RECEPTS REQ`D. SHOWN ON |
| | LOAD CALCS. |
| | 4)NOTE: PLEASE SEE 700-12E FOR CIRCUIT- |
| | -ING OF EXT/EM LTS. ON SAME BRANCH |
| | CIRCUIT AS GEN LT IN SAME AREAS. |
| | |
| | 5)NOTE: PLEASE CORRELATE PANEL SCHEDULE |
| | AND LOAD CALCULATIONS. WATER HEATER |
| | SHOWN AS 3500W ON PANEL AND 3000W ON |
| | LOAD CALCS? |
| | |
| | 6)NOTE; PLEASE SHOW ALL CONTINUOUS LOADS |
| | AT 125%. 215-3/230-42 ETC. |
| | |
| | 7)NOTE: PLEASE SHOW/CLARIFY HOW FEED |
| | IS GETTING FROM METER TO PANEL. AS PER |
| | LOCAL AMENDMENTS, NO MORE THAN 8' OF |
| | UNPROTECTED CONDUCTORS INSIDETHE BLDG. |
| | 230-70 |
| | A MAIN DISC/OCP MAY BE REQ`D OUTSIDE |
| | OR PANEL LOCATION MAY NEED TO BE MOVED? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |