Plan Review Notes
Plan Review Notes For Permit 03040476
Permit Number 03040476
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-15 00:00:00************** UNSAT ********
  
 1)NOTE: PLEASE SEE 250-24/ AN EQUIPMENT
 GROUNDING CONDUCTOR IS SHOWN ON RISER
 AND FROM METER TO MAIN BRK PANEL.
 AN EQUIPMENT GRND IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 2)NOTE: PLEASE SEE 600-5 FOR MISSING
 REQ`D SIGN CIRCUIT.
  
 3)NOTE: PLEASE SEE 210-62 FOR MISSING
 SHOW WINDOW RECEPTS REQ`D. SHOWN ON
 LOAD CALCS.
 4)NOTE: PLEASE SEE 700-12E FOR CIRCUIT-
 -ING OF EXT/EM LTS. ON SAME BRANCH
 CIRCUIT AS GEN LT IN SAME AREAS.
  
 5)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 AND LOAD CALCULATIONS. WATER HEATER
 SHOWN AS 3500W ON PANEL AND 3000W ON
 LOAD CALCS?
  
 6)NOTE; PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215-3/230-42 ETC.
  
 7)NOTE: PLEASE SHOW/CLARIFY HOW FEED
 IS GETTING FROM METER TO PANEL. AS PER
 LOCAL AMENDMENTS, NO MORE THAN 8' OF
 UNPROTECTED CONDUCTORS INSIDETHE BLDG.
 230-70
 A MAIN DISC/OCP MAY BE REQ`D OUTSIDE
 OR PANEL LOCATION MAY NEED TO BE MOVED?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372