| Plan Review Notes For Permit 03040417 |
| Permit Number |
03040417 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-01 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-RESUBMIT STORM SHUTTERS INFORMATION W/ | | | UPDATED SBCCI REPORT. CHECK DESIGN | | | PRESSURES AND PANEL MAX/MIN. SPAN. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | | 2-REVISE/CLAIFY DETAIL S-21 FOR COLUMN | | | BETWEEN STAIRWAY AND GARAGE TO MATCH | | | 2ND FLOOR FRAMING PLAN. | | | 3-RESUBMIT ENERGY CALCULATIONS WITH THE | | | ENGINEER'S ORIGINAL SIGNATURE & SEAL. | | | CHAPTER 471 FLORIDA STATUTES AND SEC. | | | 103.0 CHAPTER 13 FBC 2001. |
|