| Plan Review Notes For Permit 03040159 |
| Permit Number |
03040159 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-16 00:00:00 | PLAN REVIEW NOT A PERMIT APPLICATION. | | | | | | AT TIME OF PERMIT APPLICATION, THE PLANS | | | SHOULD INCLUDE THE SPECIFIC EFIS | | | SYSTEM TO BE USED. | | | | | | THE CLASSROOM WINDOWS MUST COMPLY WITH | | | FBC 1005.4.2, (EMERGENCY ESCAPE), IF | | | THEY THEY DO NOT MEET THE EXCEPTIONS. | | | | | | IF TEST OF NOTICE OF ACCEPTANCE REPORTS | | | FOR THE DOORS, WINDOWS AND ROOF COVERING | | | ARE NOT INCLUDED WITH THE PERMIT | | | APPLICATION, A SEPARATE PERMIT AND FEES | | | WILL BE REQUIRED. | | | | | | THE NEW STORAGE BUILDING MAY BE SUBJECT | | | TO IMPACT FEES COLLECTED BY THE COUNTY. | | | THE PERMIT PLANS MUST BE STAMPED BY THAT | | | OFFICE AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. |
|