2003-09-26 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW. PLEASE CORRELATE RISER WITH
 PANELS. PLEASE SEE THAT NOW MORE LOADS
 HAVE BEEN ADDED TO PANEL SCHEDULE WITH
 LESS LOAD? PLEASE SEE THAT THIS IS NOW
 DUE TO PANEL VOLTAGE BEING SHOWN AT 277/
 480V??? PLEASE SEE RISER, PANEL IS SHOWN
 AT 120/208V?? PLEASE CORRELATE AND
 RECONFIGURE LOAD CALCAULTIONS.
 215.5
  
 2)NOTE: PLEASE SEE WRONG NEC CODE REF.
 PLANS REF CODE FROM 1996 NEC?? 250-94
 PLEASE SEE AND REF 250.66 FROM THE 99
 NEC FOR
  
 3)NOTE: PLEASE SEE THAT TRANSFORMERS
 ARE STILL NOT SHOWN BEING GROUNDED PER
 250.30 RISER SHOWS NONE AND DETAIL SHOWS
 ??
  
 4)NOTE: PLEASE TAKE OUTALL OLD/VOIDED
 SHEETS AND INSERT NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 PLEASE SEE COPY OF FS 553.80(2)(B)
 WITH RESPECT TO DESIGN PROFESSIONAL.