| Plan Review Notes For Permit 03040146 |
| Permit Number |
03040146 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2003-09-26 00:00:00 | *********** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS | | | REVIEW. PLEASE CORRELATE RISER WITH | | | PANELS. PLEASE SEE THAT NOW MORE LOADS | | | HAVE BEEN ADDED TO PANEL SCHEDULE WITH | | | LESS LOAD? PLEASE SEE THAT THIS IS NOW | | | DUE TO PANEL VOLTAGE BEING SHOWN AT 277/ | | | 480V??? PLEASE SEE RISER, PANEL IS SHOWN | | | AT 120/208V?? PLEASE CORRELATE AND | | | RECONFIGURE LOAD CALCAULTIONS. | | | 215.5 | | | | | | 2)NOTE: PLEASE SEE WRONG NEC CODE REF. | | | PLANS REF CODE FROM 1996 NEC?? 250-94 | | | PLEASE SEE AND REF 250.66 FROM THE 99 | | | NEC FOR | | | | | | 3)NOTE: PLEASE SEE THAT TRANSFORMERS | | | ARE STILL NOT SHOWN BEING GROUNDED PER | | | 250.30 RISER SHOWS NONE AND DETAIL SHOWS | | | ?? | | | | | | 4)NOTE: PLEASE TAKE OUTALL OLD/VOIDED | | | SHEETS AND INSERT NEW SHEETS INTO TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW.IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | PLEASE SEE COPY OF FS 553.80(2)(B) | | | WITH RESPECT TO DESIGN PROFESSIONAL. |
|