| Plan Review Notes For Permit 03040146 |
| Permit Number |
03040146 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-08-26 00:00:00 | ********* UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS | | | TWO REVIEWS. PLEASE SEE NEW PANEL IN | | | KIOSK DOES NOT SHOW ANY FEEDS OR BRANCH | | | CIRCUITING FOR GATE POWER. | | | PLEASE CLARIFY WHERE POWER IS COMING | | | FROM FOR GATES? SEE FIRE REVIEW NOTES. | | | | | | 2)NOTE: PLEASE CLARIFY GROUNDING FOR | | | TRANSFORMER PER 250.30 | | | | | | PLEASE SEE ZONING NOTES FOR KIOSK TO BE | | | UNDER SEPARATE PERMIT.. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | GATES AND SUBMIT BLDG UNDER SEPARATE | | | PERMIT WITH PLANS. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|