| Plan Review Notes For Permit 03040129 |
| Permit Number |
03040129 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-02 00:00:00 | **********CORRECTIONS************ | | | | | | 1.)SITE SPECIFIC PRODUCT APPROVALS | | | FOR DOORS CANNOT BE MASTERED.SUBMIT | | | A PRODUCT APPROVAL FOR THE FRONT DOOR. | | | ALSO NOTE THAT THE SITE SPECIFIC IN | | | THE PRODUCT APPROVAL MASTER BOOK DOES | | | NOT MATCH THE PRODUCT ON THE PLAN. | | | | | | 2.)FYI - PRODUCT APPROVAL FOR THE | | | MULLIONS EXPIRES 5/1/03. | | | | | | 3.)KEY NOTE 37 REFERS TO A DETAIL | | | NOT ON THE PLAN. | | | | | | 4.)KEY NOTE 44 REFERS TO A DETAIL NOT | | | ON THE PLAN. | | | | | | 5.)PROVIDE SOILS REPORT. | | | | | | 6.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 7.)TRUSS CONNECTOR SCHEDULE A3 REFERS | | | TO THE USP 2001 CATALOG.USE THE MOST | | | RECENT CATALOG, 2003, WHICH HAS NEW | | | UPLIFT VALUES. | | | | | | 8.)PROVIDE STORM PANEL INSTALLATION | | | SCHEDULE. | | | | | | 9.)ADDITIONAL FEES REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] |
|