Plan Review Notes
Plan Review Notes For Permit 03040100
Permit Number 03040100
Review Stop P
Sequence Number 1
Notes
Date Text
2003-04-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 RM 102A SINK SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL ALL SUB-
 SECTIONS. PLEASE PROVIDE DETAILS.
 2) SHT A-1 SHOW 5' TURNING RADIUS IN ALL
 TOILET ROOMS. 11-4.22.3
 3) SHT A2 TOILET ROOM #221 TO BE ACCESS-
 IBLE PER 11-4.1.3(11). PLEASE SHOW DE-
 TAILS PER 11-4.23 AND ALL SUBSECTIONS.
 4) SHT M-2 WATER ISOMETRIC,
 A) SHUT OFF VALVE REQUIRED ON WATER
 HEATER. SEC 606.1(7).
 B) SHUT OFF VALVES REQUIRED FOR RE-
 CIRCULATING PUMP. SEC 606.2(3)
 C) THERMAL EXPANSION CONTROL REQUIRED
 PER SECTION 607.3.2
 D) A WATER HAMMER ARRESTOR SHALL BE IN-
 STALLED WHERE QUICK CLOSING VALVES ARE
 UTILIZED. (WASH MACHINES - DISH WASHERS
 AND ICE MAKERS) FBC-2001 SEC 604.9
 LOCATED NEAR THE FIXTURE IN AN "EFFECT-
 IVE RANGE" PER PDI-WH 201 AND MANUF. IN-
 STALLATION INSTRUCTIONS. NOT AT THE TOP
 OF THE DROPS IN THE CEILING.
 5) AN RPZ BACKFLOW IS REQUIRED ON WATER
 SERVICE.
 6) SHT M-1 CONDENSATE LINE SHALL HAVE A
 RELIEF VENT, (OVERFLOW), AS IT EXITS THE
 BLDG.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692