| Plan Review Notes For Permit 03040100 |
| Permit Number |
03040100 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-24 00:00:00 | DENIED: | | | PLEASE CLARIFY THE FOLLOWING INFORMATION | | | | | | 1.PLAN SHEET A-1 INDICATES ROOM #104 | | | AS A RATED ROOM.PLEASE NOTE 14" X 22" | | | SUPPLY DUCT RUNS THROUGH ROOM, NO FIRE | | | DAMPERS ARE INDICATED. | | | | | | 2.PLAN DOES NOT INDICATE A SEPARATION | | | BETWEEN PARKING GARAGE AND OFFICE SPACE. | | | AS PER 2001 FBC TABLE 704 A 1 HOUR | | | SEPARATION IS REQUIRED. | | | | | | 3.PLAN SHEET M-3 CLOSET #203, 14" X | | | 14" DUCT PENETRATES RATED PARTITION, | | | DAMPER NOT INDICATED.PLEASE CLARIFY. | | | | | | 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | OR SMOKE DETECTOR SHALL ACTIVATE A | | | VISIBLE & AUDIBLE SUPERVISORY SIGNAL | | | AT A CONSTANTLY ATTENDED LOCATION. | | | | | | 5.SEE BUILDING PLAN REVIEW COMMENTS | | | ON VENTILATION FOR PARKING GARAGE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|