| Plan Review Notes For Permit 03040100 |
| Permit Number |
03040100 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-04 00:00:00 | 1) HOW IS EXITING ACCOMPLISHED FROM | | | THE FIRST LEVEL OF THE GARAGE WITH THE | | | GATES,FENCES AND WALLS BEING PRESENT. | | | | | | 2) THE PROPOSED BUILDING MAY BE | | | LOCATED IN THE CITY FIRE LIMITS. | | | PLEASE SEE APPENDIX F OF THE LOCAL | | | AMENDMENTS OF THE FLORIDA BUILDING | | | CODE. | | | | | | 3) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. | | | | | | 4) PLEASE INDICATE EXIT DISCHARGE | | | WIDTH AND HEIGHTS FROM ANY ADJACENT | | | ONSTRUCTIONS,EQUIPMENT,OR PROPERTIES. | | | | | | 5) TACTILE SIGNAGE REQUIRED AT STAIRWELL | | | DOORS. | | | | | | 6) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENTS FOR ALL HANDRAILS | | | AND OR GAURDRAILS. | | | | | | 7) A MINIMUM OF AT LEAST TWO HOUR | | | FIRE SEPARATION IS REQUIRED BETWEEN THE | | | PARKING AREA AND OTHER PORTIONS OF | | | THE BUILDING. | | | | | | 8) HOW DOES EXITING OCCUR FROM STAIR | | | # 3 WHEN IT EMPTIES INTO A PARKING | | | AREA WITH GATES AND OTHER OBSTRUCTIONS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|