| Plan Review Notes For Permit 03040100 |
| Permit Number |
03040100 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-11 00:00:00 | ********** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE E-2, EXIT SIGNS SEEM | | | TO BE MISSING ON SECOND FLOOR. | | | PER LIFE SAFETY/NFPA-72 ETC. 700 NEC | | | | | | 2)NOTE: PLEASE CLARIFY PROVISIONS TO | | | MEET 110-26A-3. GUTTER MAY NOT PROTRUDE | | | 6" OUT FROM METER AND FUTURE DISC/? | | | | | | 3)NOTE: PLEASE CLARFIY/VERIFY ELECTRICAL | | | SERVICE LAYOUT. SHOWN DIFFERENTLY ON | | | E-1. PLEASE SEE CLEARENCE REQ`D. 110-26 | | | | | | 4)NOTE: PLEASE SEE E-2, SHOWS AHU-6 AS | | | 2-P60A AND PANEL SCHEDULE SHOWS AS 2P50A | | | PLEASE CORRELATE. | | | PLEASE ALSO SEE AMPERAGES FIGURED FOR | | | OCP OF AHU. PLEASE RE-FIGURE FOR 208V | | | AND SIZE OCP ACCORD TO 424-3B | | | PLEASE ADJUST AWG/CONDUIT. | | | | | | PLEASE SEE ANY OTHER COMMENTS FROM | | | OTHER REVIEWERS THAT MAY AFFECT ELEC. | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|