Plan Review Notes
Plan Review Notes For Permit 03040100
Permit Number 03040100
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-22 00:00:00STAIR #3 IS SHOWN EXITING INTO THE
 LOADING ZONE ON SHEET C-1.THE DOOR
 MUST NOT BE BLOCKED.SEE FBC 1001.1.3
 AND 1010.1.1.
  
 DOORS SHOWN AS 107, 118 AND 109 WILL NOT
 COMPLY WITH FBC 1003.2.3 FOR 32" CLEAR.
  
 THE PARKING GARAGE AS SHOWN MUST COMPLY
 WITH THE VENTILATION REQUIREMENTS OF
 FBC 411.4.
  
 SHEETS C-1 AND A4 APPEAR TO INDICATE A
 STEP AT THE ENTRANCES OF THE BUILDING
 THAT MAY NOT COMPLY WITH HANDICAP
 ACCESSIBILITY.PLEASE CLARIFY.SEE
 FBC 11- 4.1.3.
  
 THE ENERGY CODE MUST BE SIGNED BY THE
 DESIGN PROFESSIONALS.FBC 13-103.1.1.1.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.