Plan Review Notes
Plan Review Notes For Permit 03040099
Permit Number 03040099
Review Stop M
Sequence Number 2
Notes
Date Text
2003-07-16 00:00:00PROVISO:
  
 DUCT SMOKE DETECTOR TO BE INSTALLED IN
 THE SUPPLY AIR DUCT NOT THE RETURN AS
 INDICATED ON PLAN M-1 AS PER 2001 FBC(M)
 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.