Plan Review Notes
Plan Review Notes For Permit 03040099
Permit Number 03040099
Review Stop P
Sequence Number 1
Notes
Date Text
2003-04-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT F1 EQUIPMENT SCHEDULE, #'S 27 &
 48 NOT FOUND. PLEASE CLAIRFY
 2) SHT F1 EQUIPMENT SCHENULE #28 IN
 TOILET ROOM. PLEASE CLAIRFY
 3) SHT P-1 PLUMBING PLAN NOTES: #10 VENT
 OFFSET, EVERY DRY VENT SHALL RISE VERTI-
 CALLY TO A MINIMUM OF 6" ABOVE TH FLOOD
 LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED
 FIXTURE BEING VENTED. SECTION 905.4 &
 905.5
 4) SHT P-1 OCCUPANCY CALCULATIONS SHALL
 BE FIGURED BY FBC-2001 BLDG TABLE 1003.1
 & PLUMBING TABLE 403.1, NOT SFBC. PLEASE
 CHANGE REFERENCE.
 5) RPZ BACKFLOW REQUIRED ON WATER SERV-
 ICE.
 6) SHT P-2 WATER HEATER DETAIL, DIELECT-
 RIC UNIONS NOT APPROVED FOR WATER.
 PLEASE REMOVE REFERENCE.
 7) PLEASE SUBMIT DETAILS FOR TOILET ROOM
 PER SECTION 11-4.22, 11-4.16, & 11-4.19
 AND ALL SUBSECTIONS.
 8) PLEASE SUBMIT DETAIL FOR DRINKING
 FOUNTAIN PER SECTION 11-4.15 AND ALL
 SUBSECTIONS. ALSO PROVISIONS SHALL BE
 MADE FOR THOSE WHO HAVE DIFFICULTY BEND-
 ING OR STOOPING. SECTION 11-4.1.3(10)(A)
  
 REVIEW BY KEN STEVENS