| Notes |
| Date |
Text |
| 2003-08-26 00:00:00 | *********** UNSAT ***************** | | | | | | PLEASE SEE THAT PLANS SUBMITTED NOW BY | | | STH SHOW ALL NEW WORK BEING PERFORMED | | | FOR ELECTRICAL, THAT WAS NOT ON ORIG | | | PLANS SUBMITTED. PLEASE SEE THE FOLLOW- | | | -ING COMMENTS. | | | | | | 1)NOTE: PLEASE CLARIFY NEW OCP TO FEED | | | NEW GUTTER WHICH FEEDS A&B PANELS. | | | 215.5/240.3/310.16/250.122 | | | | | | 2)NOTE: PLEASE CLARIFY CONDUCTOR SIZE | | | PANEL "B" FEED. SHOWN FOR NEW "A" BUT | | | NOT FOR "B"? | | | | | | 3)NOTE: PLEASE CORRELATE CIRCUITING ON | | | PLANS WITH #'S ON PANEL SCHEDULE. | | | A/C? WATER HEATER? ETC. | | | | | | 4)NOTE: PLEASE VERFIY OCP FOR A/C SYS.? | | | \\MAX 150%? | | | PLEASE ALSO SIZE MAX OCP FOR WATER HEAT | | | AT OR BELOW 150%. MIN 125% 422.13,422.11 | | | E-3 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REIVEW | | | 561-805-6717 | | | [email protected] |
|