Plan Review Notes
Plan Review Notes For Permit 03040098
Permit Number 03040098
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-2 OTHER TOILET ROOMS PROVIDED
 FOR THE USE OF OCCUPANTS OF SPECIFIC
 SPACES (I.E., A PRIVATE TOILET ROOM FOR
 THE OCCUPANT OF A PRIVATE OFFICE) SHALL
 BE ADAPTABLE. SUBMIT DETAILS FOR THE
 PRIVATE BATHROOM. SHOW TURNING RADIUS,
 CENTER LINE OF WATER CLOSET TO WALL,
 BACKING FOR ALL GRAB BARS, (W/C & SHWR),
 CURB FOR SHOWER, CONTROLS FOR SHOWER ECT
 SECTIONS 11-4.22.3, FIGURE 28, 11-4.16.4
 11-4.21.7, 11-4.21.5, 11-4.21.4 ECT.
 2) SHT A-2 TABLE 403.1 A DRINKING FOUNT-
 AIN IS REQUIRED. (ALSO SEE SEC 410.1)
 3) SHTS A-5/A-6 PLEASE SHOW CLEAR FLOOR
 SPACE FOR URNAL. 11-4.18.3.
 4) SHT P-2 GENERAL NOTES #16 AIR CHAMB-
 ERS ARE NOT APPROVED. PLEASE DELETE REF-
 ERENCE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692