| Plan Review Notes For Permit 03040098 |
| Permit Number |
03040098 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A-2 OTHER TOILET ROOMS PROVIDED | | | FOR THE USE OF OCCUPANTS OF SPECIFIC | | | SPACES (I.E., A PRIVATE TOILET ROOM FOR | | | THE OCCUPANT OF A PRIVATE OFFICE) SHALL | | | BE ADAPTABLE. SUBMIT DETAILS FOR THE | | | PRIVATE BATHROOM. SHOW TURNING RADIUS, | | | CENTER LINE OF WATER CLOSET TO WALL, | | | BACKING FOR ALL GRAB BARS, (W/C & SHWR), | | | CURB FOR SHOWER, CONTROLS FOR SHOWER ECT | | | SECTIONS 11-4.22.3, FIGURE 28, 11-4.16.4 | | | 11-4.21.7, 11-4.21.5, 11-4.21.4 ECT. | | | 2) SHT A-2 TABLE 403.1 A DRINKING FOUNT- | | | AIN IS REQUIRED. (ALSO SEE SEC 410.1) | | | 3) SHTS A-5/A-6 PLEASE SHOW CLEAR FLOOR | | | SPACE FOR URNAL. 11-4.18.3. | | | 4) SHT P-2 GENERAL NOTES #16 AIR CHAMB- | | | ERS ARE NOT APPROVED. PLEASE DELETE REF- | | | ERENCE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|