Plan Review Notes
Plan Review Notes For Permit 03032421
Permit Number 03032421
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-10 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250-66. PLEASE NOTE, SEC`S
 ARE BASED ON 310-15FOR 400A SERVICE.
  
 2)NOTE: PLEASE SUBMIT PANEL SCHEDULE FOR
 PANEL "C" AS SHOWN ON RISER?
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING COND FROM MAIN DISC TO PANEL
 "B". 250-122
  
 4)NOTE: SD NOT PERMITTED IN KITCHEN
 PER NFPA-72 8-1.4.2
  
 5)NOTE: PLEASE SEE 220-16 FOR MIN KW FOR
 WASHER CIRCUIT. 1.5KW
  
 6)NOTE: PLEASE SEE MISSING REQ`DBATH
 CIRCUIT(S) 210-52D/210-11C-3
  
 PLEASE VERIFY SIZE OF SERVICE WITH
 CONTRACTOR.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEYPALMER
 ELECTRICAL PLANREVIEW
 561-659-8096 EXT 8372
 [email protected]