| Plan Review Notes For Permit 03032421 |
| Permit Number |
03032421 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-10 00:00:00 | ************* UNSAT *************** | | | | | | 1)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | | CONDUCTOR PER 250-66. PLEASE NOTE, SEC`S | | | ARE BASED ON 310-15FOR 400A SERVICE. | | | | | | 2)NOTE: PLEASE SUBMIT PANEL SCHEDULE FOR | | | PANEL "C" AS SHOWN ON RISER? | | | | | | 3)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING COND FROM MAIN DISC TO PANEL | | | "B". 250-122 | | | | | | 4)NOTE: SD NOT PERMITTED IN KITCHEN | | | PER NFPA-72 8-1.4.2 | | | | | | 5)NOTE: PLEASE SEE 220-16 FOR MIN KW FOR | | | WASHER CIRCUIT. 1.5KW | | | | | | 6)NOTE: PLEASE SEE MISSING REQ`DBATH | | | CIRCUIT(S) 210-52D/210-11C-3 | | | | | | PLEASE VERIFY SIZE OF SERVICE WITH | | | CONTRACTOR. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEYPALMER | | | ELECTRICAL PLANREVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|