| Date |
Text |
| 2003-05-01 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-PROVIDE SOIL TEST REPORT PRIOR TO |
| | CONSTRUCTION. |
| | 2-SHEET C-1: SPECIFY THE APPLICABLE |
| | INTERNAL PRESSURE COEFFICIENT ON THE |
| | DESIGN INFORMATION AS REQUIRED BY SEC. |
| | 1606.1.7 FBC 2001. |
| | 3-PROVIDE COMPLETE DETAIL/SPECIFICATIONS |
| | FOR HANGING AIR HANDLER UNIT FROM |
| | TRUSSES. SPECIFY ALL FASTENERS. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 4-PROVIDE SPECIFICATIONS FOR FIREBLOCK'G |
| | AT ALL CONCEALED SPACES AS REQUIRED BY |
| | SEC. 2305 FBC 2001. INCLUDING STAIRS. |
| | 5-PROVIDE COMPLETE DETAILS AND SPECS FOR |
| | HANDRAIL HEIGHT AND OPENINGS ALLOWANCE |
| | AS REQUIRED BY SEC. 1007.5 FBC 2001. |
| | 6-SPECIFY SAFETY GLASS FOR WINDOW AT |
| | COVERED ENTRY. SEC. 2405.2 FBC 2001. |
| | 7-CLARIFY WHAT IS THE DETACHABLE SAFETY |
| | RAIL SPECIFIED ON ELEVATION ON SHEET |
| | A-4. SEC. 104.2.1.2 CITY AMENDMENTS. |
| | 8-UPDATE TRUSS SCHEDULE. SEE UPDATED |
| | USP CATALOGUE (2003). ALSO, PROVIDE |
| | ENGINEERING CALCULATIONS FOR VALUES |
| | OTHER THAN THOSE SHOWN BY USP. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | **NOTE: ALSO CONSIDER THAT IF USING 10D |
| | NAILS, THEN IT NEEDS 1 3/4" MINIMUM |
| | PENETRATION TO USE THIS VALUES. ONE |
| | TRUSS DOESN'T HAVE THIS THICKNESS. |
| | 9-ROOF FRAMING PLAN: REVISE CONNECTORS |
| | SPECIFIED FOR FRAMED WALLS. NEED WOOD |
| | TO WOOD CONNECTORS. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 10-PROVIDE COMPLETE DETAILS & STRUCTURAL |
| | INFORMATION FOR PRECAST GUARDRAIL TO |
| | BE USED ON 2ND FLOOR BALCONY.SECTION |
| | 1015 FBC 2001 AND SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 11-SHEET A-1: CLARIFY FOOTING AT GARAGE |
| | INTERIOR BEARING WALL. F8 OR TE-1?. |
| | DETAIL #2 DOESN'T APPLY AT GARAGE. |
| | REVISE AS REQUIRED. |
| | DETAIL 38 NEED 12" MIN. BELOW GRADE. |
| | 12-PROVIDE COMPLETE/CORRECT INFORMATION |
| | FOR STORM SHUTTERS UNDER A SEPARATE |
| | PERMIT. |