| Plan Review Notes For Permit 03032420 |
| Permit Number |
03032420 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-13 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE SOIL TEST REPORT PRIOR TO | | | CONSTRUCTIONNOT AT TIME OF SLAB | | | INSPECTION. DENSITY TEST IS THE ONE | | | TO BE COLLECTED AT TIME OF SLAB | | | INSPECTION. | | | 2-PROVIDE COMPLETE/CORRECT INFORMATION | | | FOR STORM SHUTTERS UNDER A SEPARATE | | | PERMIT: A)REVISE DESIGN PRESSURES. SEE | | | DESIGN PRESSURES CALCULATED BY THE | | | ARCHITECT. B)SEE ENGINEERED DRAWINGS | | | FOR MAX./MIN. PANEL SIZE ACCORDING TO | | | DESIGN PRESSURES & REVISE INSTALLATION | | | SCHEDULE AS REQUIRED. C)CLEARLY MARK/ | | | CIRCLE ON ENGINEERED DRAWINGS THE | | | MOUNTING CONDITIONS, TYPE AND ANCHOR | | | SPACING ACCORD'G TO THE EDGE DISTANCE, | | | DESIGN PRESSURES, CONNECTION TYPE, | | | PANEL SPAN & STRUCTURE TO BE ATTACHED. |
|