2003-04-10 00:00:00********** NOTES REDLINED ***********
  
 PLEASE SEE CIRCUITING FOR GEN LT IN SUB-
 PANEL. SHOWS 10 CIR AT 60A #6?
 SHOULD BE 15A/20A #14/12?
  
 1)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN PANEL
 AND SUB PANEL.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  