| Date |
Text |
| 2003-07-24 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 AMENDMENTS, CHAPTER |
| | ONE, ADMIN. CODE |
| | |
| | 1) FROM PREVIOUS REVIEW: SHOW DETAIL FOR |
| | TOILET ROOMS. FOR WATER CLOSETS SHOW |
| | CLEAR FLOOR SPACE 11-4.16.2, HEIGHT |
| | 11-4.16.3, GRAB BARS 11-4.16.4, AND |
| | FLUSH CONTROLS 11-4.16.5. FOR LAVS SHOW |
| | HEIGHT & CLEARANCES 11-4.19.2, CLEAR |
| | FLOOR SPACE 11-4.19.3, EXPOSED PIPES |
| | 11-4.19.4, AND FAUCETS 11-4.19.5. FOR |
| | BREAK ROOM SINK SHOW HEIGHT 11-4.24.2, |
| | KNEE CLEARANCES 11-4.24.3, DEPTH 11-4. |
| | 24.4, CLEAR FLOOR SPACE 11-4.24.5, EX- |
| | POSED PIPES & SURFACES 11-4.24.6, AND |
| | FAUCETS 11-4.24.7. SECTION 104.2.1 - |
| | INFORMATION SHALL BE SPECIFIC, AND THE |
| | TECHNICAL CODES SHALL NOT BE CITED AS A |
| | WHOLE OR IN PART, NOR SHALL THE TERM |
| | "LEGAL" OR ITS EQUIVALENT BE USED AS A |
| | SUBSTITUTE FOR SPECIFIC INFORMATION. |
| | 2) TOILET ROOM FOR OFFICES #'S 4 & 5 IS |
| | NOT A PRIVATE TOILET ROOM BUT A COMMON |
| | USE TOILET ROOM AND SHALL BE ACCESSIBLE. |
| | SEE COMMENT #1 FOR DETAILS REQUIRED FOR |
| | TYPICAL ACCESSIBLE TOILET ROOM. ALSO |
| | SHOW COMPLIANCE WITH 11-4.21 AND ALL |
| | SUBSECTIONS. SIZE & CLEARANCE 11-4.21.2, |
| | SEAT 11-4.21.3, GRAB BARS 11-4.21.4, |
| | CONTROLS 11-4.21.5, & CURBS 11-4.21.7 |
| | 3) NEW COMMENT, PER TABLE 403.1 A DRINK- |
| | ING FOUNTAIN IS REQUIRED. ALSO SEE SECT- |
| | ION 410.1 |
| | 4) NEW COMMENT SUBMIT A WATER RISER DIA- |
| | GRAM. WATER HAMMER ARRESTORS REQUIRED BY |
| | SECTION 604.9 (AT DISHWASHER & ICE MAKER |
| | IN REFRIG. IF INSTALLED), SHALL BE LOCA- |
| | TED NEAR THE FIXTURE IN AN "EFFECTIVE |
| | RANGE" AND NOT IN THE CEILING AT THE TOP |
| | OF THE DROPS. |
| | 5) PLEASE SEE ATTACHED SHEET CONCERNING |
| | ARCHITECTS SEAL AND TITLE BLOCK REQUIRED |
| | FOR EACH SHEET. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |