| Date |
Text |
| 2003-08-04 00:00:00 | **************** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM, |
| | PANEL ETC. PANEL SHOWN AS 225A,ON RISER, |
| | 400A ON SCHEDULE AND400A OCP FEEDING |
| | A 225A PANEL. LOAD SHOWN AT 257A'S ON |
| | A 225A PANEL? |
| | |
| | 215/310-16/240/230/ ETC |
| | |
| | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS |
| | AS REQUESTED ON FIRST REVIEW. 220 |
| | SEE ALL ART'S REFERENCED ON FIRST REVIEW |
| | |
| | 3)NOTE: PLEASE CLARIFY SOME CIRCUITING |
| | SHOWN FOR EM/EXT LTS MISSING. PLEASE SEE |
| | 700-12E FOR CIRCUITING. |
| | |
| | 4)NOTE: PLEASE CLARFIY LIGHTING SHOWN |
| | AS REQ'D SIGN CIRCUIT? SHOWN AS WHAT |
| | APPEARS TO BE FLOOD LTS? SYMBOL NOT |
| | SHOWN ON ELECTRICAL LEGEND? |
| | PLEASE SHOW REQ'D SIGN CIRCUIT AT |
| | ENTRANCE PER 600-5 |
| | |
| | 5)NOTE: PLEASE CLARIFY TWO A/C SYSTEMS |
| | NOW SHOWN ON PLANS AND ONLY ONE ON PANEL |
| | SCHEDULE? PLEASE ALSO INCLUDE ON LOAD |
| | CALCUALTIONS PER 220/215-5 |
| | CIRCUIT #'S SHOWN ON PLANS BUT DO NOT |
| | CORRELATE W/ PANEL SCHEDULE? |
| | |
| | 6)NOTE: PLEASE CLARIFY SEC`S, NOT SHOW- |
| | -ING ANY CONDUCTOR SIZE FROM METER TO |
| | MAIN? PLEASE ALSO SEE SIZE SHOWN FROM |
| | MAIN TO PANEL AS 3-# 4/0 MCM,,,? |
| | PLEASE SEE 310-16 FOR SIZING |
| | |
| | 7)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | SYSTEM, PER 250-50 GRND RD, COLD WATER |
| | ETC, IF AVAILABLE. |
| | |
| | 8)NOTE: PLEASE SEE COPY OF FS 553.80(2)- |
| | (B) W/ RESPECT TO DESIGN PROFESSIONAL. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |