| Plan Review Notes For Permit 03032368 |
| Permit Number |
03032368 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-04 00:00:00 | 1) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. | | | | | | 2) NO INTERIOR FINISH CLASSIFICATION | | | FOR THE WALLS AND CEILINGS. | | | | | | 3) RISERS FOR STAIRS NEAR SECRETARY | | | POOL AREA DOES NOT MEET CODE. | | | | | | 4) STAIRS NEAR KITCHEN DOES NOT MEET | | | CODE. | | | | | | 5) ILLUMINATED EXIT SIGNS AND EMERGENCY | | | LIGHTS SHALL BE PLACED ON THE SAME | | | DRAWING. | | | | | | 6) NO FIRE EXTINGUISHERS SHOWN ON THE | | | PLANS. | | | | | | 7) IF NO FIRE SPRINKLERS ARE PLANNED, | | | THEN STORAGE ROOMS SHALL BE FIRE | | | RATED AT LEAST ONE HOUR WITH PROPER | | | OPENING PROTECTIVES. | | | | | | 8) WRONG BUILDING CODE REFERENCED ON | | | THE PLANS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|