| Date |
Text |
| 2003-04-11 00:00:00 | THE GENERAL NOTES ON SHEET 1 DECLARES |
| | THE 1997 STANDARD BUILDING CODE.THE |
| | CITYOF WEST PALM BEACH AND THE STATE OF |
| | FLORIDA ARE CURRENTLY USING THE 2001 |
| | FLORIDA BUILDING CODE. |
| | |
| | SEE FBC 104.3.1.1 FOR THE MINIMUM |
| | CRITERIA REQUIRED FOR PLAN REVIEW. |
| | |
| | THE ADDITION OF THE SECOND FLOOR AS |
| | WELLAS THE CHANGE OF USE FROM |
| | WAREHOUSE/STORAGE TO OFFICE IS SUBJECT |
| | TO IMPACT FEES COLLECTED BY THE COUNTY. |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED THE FEES MUST BE PAID TO THE |
| | COUNTY, THE PERMIT PLANS STAMPED BY |
| | THAT OFFICE AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.CALL (561) 233-5025 FOR |
| | MORE INFORMATION. |
| | |
| | THE OPENINGS ON THE SOUTH AND EAST |
| | EXTERIOR WALLS ARE REQUIRED TO BE FIRE |
| | PROTECTED AS PROVIDED FOR IN FBC TABLE |
| | 600. |
| | |
| | OPENINGS IN THE WEST WALL ARE |
| | PROHIBITTED BY FBC TABLE 600. |
| | |
| | THE DESIGNATED FIVE FEET WIDE AISLE FOR |
| | THE HC PARKING SPACE IS NOT SHOWN ON THE |
| | SITE PLAN. SEE FBC 11- 4.6.3. |
| | |
| | VERTICAL ACCESSIBILITY IS REQUIRED FOR |
| | THE OFFICES SHOWN AS #4 & #5 AND THE |
| | SECOND FLOOR.SEE FBC 11- 4.1.6. |
| | |
| | PLEASE PROVIDE A BETTER STRUCTURAL |
| | FRAMING PLAN INCLUDING ALL OF THE |
| | DESIGN LOADS AND STANDARDS USED.SHOW |
| | THE MODIFICATIONS TO THE EXISTING WALLS |
| | IF ANY.THE PLACEMENT OF THE COLUMN AND |
| | FOOTING THAT ARE SHOWN IN SECTION ONLY. |
| | |
| | PROVIDE COMPLETE STRUCTURAL |
| | CALCULATIONSFOR THE SECOND FLOOR DESIGN. |
| | |
| | THE STAIRS MUST HAVE |
| | HANDRAILS COMPLYING WITH FBC 1007.5. |
| | |
| | THE SECOND FLOOR STAIRS ARE REQUIRED TO |
| | BE ENCLOSED IN FIRE RATED CONSTRUCTION. |
| | SEE FBC 1006.1.1. |
| | |
| | TWO MEANS OF EGRESS ARE REQUIRED FROM |
| | THE SECOND FLOOR.SEE FBC 1004.2.1 AND |
| | FBC 1027.1.1. |
| | |
| | THE 8" STAIR RISER SHOWN DOES NOT COMPLY |
| | WITH FBC 1007.3. |
| | |
| | THIS BUILDING IS LOCATED IN THE |
| | DESIGNATED FIRE DISTRICT AND EXTERIOR |
| | ARCHITECTURAL TRIM IS REQUIRED TO BE |
| | FIRE RETARDANT TREATED LUMBER OF |
| | NON-COMBUSTIBLE MATERIAL.SEE FBC |
| | F102.2.7 AS AMENDED BY THE CITY OF WEST |
| | PALM BEACH. |
| | |
| | PLEASE PROVIDE THREE COPIES OF SIGNED |
| | AND SEALED ENERGY CODE CALCLULATIONS. |
| | SEE FBC 13- 101.3. |