| Plan Review Notes For Permit 03032245 |
| Permit Number |
03032245 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-09 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE: PLEASE CORRELATE PANEL SCHEDULES | | | / LOAD CALCULATIONS. PLEASE REVISE LOAD | | | CALCULATIONS.220-3 | | | SOME LOADS MISSING ON LOAD CALCS. | | | BOTH SUB-PANELS ARE NOT SHOWN ON MAIN | | | PANEL SCHEDULE? | | | POOL EQUIPMENT LOADS NEED TO CORRELATE | | | W/ LOAD CALCS. | | | PANEL MENTIONS EXISTING 2P-70A AND | | | PANEL SCHEDULE FOR MAIN PANEL SHOWS | | | ONLY ONE SUB PANEL AND IT IS SHOWN AT | | | 60A?? PLEASE CORRRELATE. | | | | | | 2)NOTE: PLEASE SHOW LOCATION OF NEW | | | PANEL AND GROUPING OF MAINS PER 230-72 | | | | | | 3)NOTE: PLEASE SEE PLANS, TWO DIFFERENT | | | EXISTING RISER DIAGRAMS SUBMITTED FOR | | | REVIEW? PLEASE ONLY SUBMIT THE ACTUAL | | | EXISTING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected]. |
|