Plan Review Notes
Plan Review Notes For Permit 03032245
Permit Number 03032245
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-09 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE PANEL SCHEDULES
 / LOAD CALCULATIONS. PLEASE REVISE LOAD
 CALCULATIONS.220-3
 SOME LOADS MISSING ON LOAD CALCS.
 BOTH SUB-PANELS ARE NOT SHOWN ON MAIN
 PANEL SCHEDULE?
 POOL EQUIPMENT LOADS NEED TO CORRELATE
 W/ LOAD CALCS.
 PANEL MENTIONS EXISTING 2P-70A AND
 PANEL SCHEDULE FOR MAIN PANEL SHOWS
 ONLY ONE SUB PANEL AND IT IS SHOWN AT
 60A?? PLEASE CORRRELATE.
  
 2)NOTE: PLEASE SHOW LOCATION OF NEW
 PANEL AND GROUPING OF MAINS PER 230-72
  
 3)NOTE: PLEASE SEE PLANS, TWO DIFFERENT
 EXISTING RISER DIAGRAMS SUBMITTED FOR
 REVIEW? PLEASE ONLY SUBMIT THE ACTUAL
 EXISTING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected].