| Plan Review Notes For Permit 03032205 |
| Permit Number |
03032205 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-10 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | COMMENTS FROM PREVIOUS REVIEW NOT ADD- | | | RESSED. SEE NEW SHT P-1.1 | | | 1) SHT P-1.1 DISHWASHER SHALL DRAIN INTO | | | SANITARY NOT GREASE WASTE. UTILITY ORD. | | | 2) ALL ABANDONED/CAPPED PIPES SHALL BE | | | INSPECTED PRIOR TO COVERING. | | | 3) SHT P-1.1, 3 COMPARTMENT SINK SHALL | | | DRAIN TO GREASE WASTE. | | | 4) SHT P-1.1 ALL INDIRECT WASTE SHALL | | | DRAIN TO FLOOR SINKS. SEC 802.3 - FLOOR | | | DRAINS ARE NOT AN APPROVED INDIRECT | | | WASTE RECEPTOR. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|