| Plan Review Notes For Permit 03032191 |
| Permit Number |
03032191 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-18 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | | | | 1) SHT P-18 GAS ISOMETRIC, REFERENCE | | | NFPA-54 (1996) - NFPA-54 NOT ADOPTED IN | | | FBC-2001. PLEASE INDICATE CODE IN FBC- | | | 2001 FUEL GAS CODE THAT WILL SHOW 400' | | | DEVELOPED LENGTH @ 2PSI. | | | 2) SHT P-18 GAS ISOMETRIC, LINE SUPPLY- | | | ING REGULATOR #2 SHOWS 1775 MBH, BUT | | | ONLY SHOWS 2 @ 400 MBH & 1 @ 200 MBH = | | | 1000 MBH. PLEASE CLAIRFY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|