| Plan Review Notes For Permit 03032166 |
| Permit Number |
03032166 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-09-16 00:00:00 | ********** UNSAT ************* | | | | | | 1)NOTE: PLEASE CORRELATE PANEL SIZES | | | AND RISER DIAGRAM. | | | RISER SHOWS 3-150A MCB PANELS, AND PANEL | | | ARE INDICATED AS 2-200A AND 1-60A. | | | | | | 2)NOTE: PLEASE SHOW LOCATIONS FOR ALL | | | PANELS. A&B APPEARS TO BE PANELS IN | | | GARAGE?? | | | | | | 3)NOTE: PLEASE SEE MISSING RECEPTS FOR | | | 2' OF WALL SPACE. 210.52 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|