2004-09-16 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE CORRELATE PANEL SIZES
 AND RISER DIAGRAM.
 RISER SHOWS 3-150A MCB PANELS, AND PANEL
 ARE INDICATED AS 2-200A AND 1-60A.
  
 2)NOTE: PLEASE SHOW LOCATIONS FOR ALL
 PANELS. A&B APPEARS TO BE PANELS IN
 GARAGE??
  
 3)NOTE: PLEASE SEE MISSING RECEPTS FOR
 2' OF WALL SPACE. 210.52
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  