Plan Review Notes
Plan Review Notes For Permit 03032166
Permit Number 03032166
Review Stop B
Sequence Number 2
Notes
Date Text
2003-08-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03032166
 ADD: 6660 AUDUBON TRACE
 CONT: GHO DEVELOPMENT
 TEL: (561)688-2080
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 SECOND REVIEW
 ACTION: DENIED
  
 1) SHEET A-6 TRUSS ANCHOR SCHEDULE FOR
 THE RT-22 STRAP, ALLOWABLE LOAD 1125
 PER STRAP.
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 2)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 MIAMI-DADE OR SBCCI ARE ACCEPTABLE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 THE (2) NORANDEX REPORTS THAT HAVE
 MIAMI-DADE APPROVAL DO NOT REQUIRE THE
 SITE SPECIFIC ENGINEERING.
 THE REMAINDER OF THE NORANDEX REPORTS
 THAT ARE LARGE MISSLE IMPACT RATED WILL
 REQUIRE SITE SPECIFIC ENGINEERING, USING
 THE CITY OF WPB FORM. THE ENGINEER FROM
 NORANDEX FILLS OUT THE LEFT SIDE AND
 SIGNS AND SEALS THE FORM. THE DESIGN
 PROFESSIONAL FOR THE STRUCTURE FILLS OUT
 THE RIGHT SIDE AND SIGNS AND SEALS THIS
 SIDE OR A COVER LETTER INDICATING THIS
 PRODUCT WILL MEET THE CODE REQUIREMENTS
 FOR HIS DESIGN.
  
 3)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY (DADE COUNTY OR SBCCI) OR
 SITE SPECIFIC ENGINEERING.
  
 4)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved