Plan Review Notes
Plan Review Notes For Permit 03032132
Permit Number 03032132
Review Stop B
Sequence Number 2
Notes
Date Text
2003-04-07 00:00:00**********CORRECTIONS************
  
 1.)THE BEDROOM WINDOWS DO NOT MEET
 EGRESS OPENING REQUIREMENTS:
 2001 FL BLD CODE, 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGTH OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR.
  
 2.)ON RESUBMITTAL, PLEASE CLEARLY
 MARK BEDROOM WINDOWS ON THE ELEVATIONS
 OR INDICATE NORTH ON THE FLOOR PLANS.
  
 3.)THE HURRICANE SHUTTERS SELECTED
 DO NOT APPEAR TO MEET EGRESS
 REQUIREMENTS FOR THE BEDROOM WINDOWS.
 PLEASE CLARIFY.
  
 4.)PLEASE ADDRESS COMMENT #4 FROM
 THE PREVIOUS CORRECTION NOTICE.PROVIDE
 MULLION PRODUCT APPROVALS.
  
 5.)PLEASE ADDRESS COMMENT #5 FROM
 THE PREVIOUS CORRECTION NOTICE.
  
 WHEN RESUBMITTING PLANS PLEASE CLEARLY
 INDICATE THE REVISION AND SUBMIT ONE
 SET OF THE OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, WILL HELP TO EXPEDITE
 YOUR PERMIT.
  