| 2003-04-07 00:00:00 | **********CORRECTIONS************ |
| | |
| | 1.)THE BEDROOM WINDOWS DO NOT MEET |
| | EGRESS OPENING REQUIREMENTS: |
| | 2001 FL BLD CODE, 1005.4: |
| | PROVIDE EMERGENCY EGRESS WINDOWS IN |
| | SLEEPING ROOMS WITH A MINIMUM NET CLEAR |
| | OPENING HEIGTH OF 24" AND NET CLEAR |
| | OPENING WIDTH OF 20" AND A NET CLEAR |
| | OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR |
| | OPENINGS ARE PERMITTED TO HAVE A NET |
| | CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH |
| | SHALL NOT BE MORE THAN 44 " ABOVE THE |
| | FINISH FLOOR. |
| | |
| | 2.)ON RESUBMITTAL, PLEASE CLEARLY |
| | MARK BEDROOM WINDOWS ON THE ELEVATIONS |
| | OR INDICATE NORTH ON THE FLOOR PLANS. |
| | |
| | 3.)THE HURRICANE SHUTTERS SELECTED |
| | DO NOT APPEAR TO MEET EGRESS |
| | REQUIREMENTS FOR THE BEDROOM WINDOWS. |
| | PLEASE CLARIFY. |
| | |
| | 4.)PLEASE ADDRESS COMMENT #4 FROM |
| | THE PREVIOUS CORRECTION NOTICE.PROVIDE |
| | MULLION PRODUCT APPROVALS. |
| | |
| | 5.)PLEASE ADDRESS COMMENT #5 FROM |
| | THE PREVIOUS CORRECTION NOTICE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE CLEARLY |
| | INDICATE THE REVISION AND SUBMIT ONE |
| | SET OF THE OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, WILL HELP TO EXPEDITE |
| | YOUR PERMIT. |
| | |