| Plan Review Notes For Permit 03032038 |
| Permit Number |
03032038 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-21 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-RESUBMIT STORM SHUTTERS INFORMATION | | | WITH UPDATED SBCCI PRODUCT APPROVAL | | | THAT MATCHES ENGINEERED DRAWINGS. | | | CHECK DESIGN PRESSURES SHOWN ON THE | | | INSTALLATION SCHEDULE & PANEL MAX/MIN | | | SPAN SHOWN ON ENGINEERED DRAWINGS. | | | 2-RESUBMIT ENERGY CALCULATIONS WITH | | | ENGINEER'S ORIGINAL SIGNATURE & SEAL. | | | CHAPTER 471 FLORIDA STATUTES AND SEC. | | | 103.0 CHAPTER 13 FBC 2001. | | | 3-SPECIFY DETAIL AT TOP OF WOOD COLUMN | | | BY THE STAIRS. SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. |
|