Plan Review Notes
Plan Review Notes For Permit 03032015
Permit Number 03032015
Review Stop P
Sequence Number 2
Notes
Date Text
2003-04-15 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) HAND DRAWN CORRECTIONS ON SIGNED AND
 SEALED PLANS SHALL BE INITALED AND DATED
 BY ENGINEER OF RECORD.
 2) TWO COPIES REQUIRED FOR ALL INFOR-
 MATION SUBMITTED.
 3) NEW PIPING SCHEMATIC, ONLY ONE HEATER
 IS SHOWN. POOL LAYOUT SHOWS 2 HEATERS,
 ONE GAS AND ONE ELECTRIC. PLEASE SHOW
 BOTH HEATERS ON SCHEMATIC.
 4) NOTE #1 STATES CPVC FLANGES WITH PVC
 BEING GLUED TO THE CPVC. THIS IS NOT
 APPROVED. PLEASE SEE MANUFACTURES INFOR-
 MATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692