2003-04-09 00:00:00************** UNSAT ***************
  
 PLEASE SEE NOTES FROM FIRST REVIEW
  
 1)NOTE: PLEASE SEE PLANS, WIRING DIAGRAM
 DOES NOT SHOW 3-PUMPS AS SHOWN ON PLUMB
 AND SUBMITTED PANEL SCHEDULE.
  
 2)NOTE: PLEASE SUBMIT PLANS AND SPECS
 FOR ONE HEATER OR THE OTHER. SUBMITTED
 BOTH ELECTRICAL AND GAS??
 ELECTRICAL WIRING DIAGRAM DOES NOTE SHOW
 EITHER? IF ELECTRIC, SUBMIT LOAD
 CALCULATIONS THAT INCLUDE NEW PUMPS AND
 HEAT PUMP. PANEL SCHEDULE SUBMITTED
 ONLY LIST ON PANEL SCHEDULE AND DOES NOT
 REVISE LOAD CALC. PLEASE ALSO SEE LOAD/
 KW LISTED ON PANEL SCHEDULE FOR HEAT
 PUMP. KW RATING DOES NOT CORRELATE
 W/ SPECS SUBMITTED.??
  
 PLEASE SEE ATTACHED LETTER FOR PLANS
 BEING REVIEW. FS 553.80(2)(B).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT8372
 [email protected]