| Plan Review Notes For Permit 03032015 |
| Permit Number |
03032015 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-02 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE PLANS, SHOWS THREE | | | PUMPS AND ONLY ONE SHOWN ON RISER DIA- | | | -GRAM? | | | | | | 2)NOTE: PLEASE SEE POOL DATA, MENTIONS, | | | GAS AND ELECTRIC HEATERS? PLEASE SEE | | | PERMIT APPLICATION, SHOWS NO HEATERS? | | | PLEASE ADJUST. | | | IF HEATERES ARE INSTALLED, PLEASE ALSO | | | SUBMIT SPECS FOR HEATER. IF ELECTRICAL | | | HEATER IS INSTALLED, PLEASE SUBMIT LOAD | | | CALCULATIONS FOR EXISTING SERVICE AND | | | NEW ADDED LOADS. | | | 215-5/220 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|