| Plan Review Notes For Permit 03031952 |
| Permit Number |
03031952 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-06-18 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE SOIL TEST REPORT. "MASTER SOIL | | | TEST" IS PRELIMINARY AND CALLS FOR | | | ADDITIONAL BORINGS ON THE LIMITATIONS. | | | 2-RESUBMIT STORM SHUTTERS: | | | A)DESIGN PRESSURES ARE LOWER THAN THOSE | | | CALCULATED BY THE ARCHITECT OF RECORD. | | | B)REVISE SIZE OF PANEL SPAN. SEE THE | | | ENGINEERED DRAWINGS FOR MIN. SIZE. | | | C)CLEARLY MARK ON THE ENGINEERED DWGS | | | ANCHOR TYPE AND SPACING TO BE USED | | | ACCORDING TO THE EDGE DISTANCE (THIS | | | MAKES A BIG DIFFERENCE ON THE ANCHOR | | | SPACING), DESIGN PRESSURE, PANEL SPAN, | | | CONNECTION TYPE AND STRUCTURE TO BE | | | ATTACHED TO. | | | | | | 3-PROVIDE STRUCTURAL BUCK DETAIL FOR | | | GARAGE DOOR. SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | 4-SPECIFY SAFETY GLASS FOR GLASS BLOCK | | | BY TUB & SHOWER AREA IF FACE THICKNESS | | | OF GLASS BLOCK IS LESS THAN 0.25". | | | SEE SEC. 2405.2 FBC 2001. |
|