2003-05-13 00:00:00BUILDING CHECKLIST:
 1-REAR ELEVATION EXCEEDS THE MAXIMUM
 PERCENTAGE OF OPENINGS ALLOWED BY
 TABLE 600 FBC 2001.
 **NOTE: TABLE 600 REFERS TO OPENINGS IN
 THE WALL AREA, NOT GLASS AREA IN THE
 OPENING.
 2-PROVIDE SOIL TEST REPORT NOW. NOT AT
 TIME OF CONCRETE SLAB. THIS IS PART
 OF PLAN REVIEW AND INFORMATION NEEDED
 BY DESIGNER TO DESIGN FOOTINGS ETC.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 3-PAY IMPACT FEES AND BRING BACK PAID
 RECEIPT AND STAMPED DRAWINGS.
 4-STORM SHUTTERS:
 A)REVISE DESIGN PRESSURES. SEE PLANS FOR
 CALCULATED PRESSURES BY THE ARCHITECT.
 B)SEE ENGINEERED DRAWINGS FOR MAXIMUM
 AND MINIMUM PANEL SPAN ACCORDING TO
 THE DESIGN PRESSURES.
 C)CLEARLY MARK/CIRCLE ON STORM SHUTTERS
 DRAWINGS THE MOUNTING CONDITIONS AND
 ANCHOR TYPE AND SPACING TO BE USED
 ACCORDING TO THE EDGE DISTANCE, DESIGN
 PRESSURES, CONNECTION TYPE, PANEL SPAN
 AND STRUCTURE TO BE ATTACHED TO.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 5-PROVIDE PRODUCT APPROVAL FOR FRENCH
 DOORS WITH SIDELITES SINGLE ASSEMBLY
 AS SHOWN ON PLANS. **BROWARD COUNTY
 PRODUCT APPROVAL IS NOT ACCEPTABLE.
 PROVIDE DADE COUNTY, SBCCI OR SITE
 SPECIFIC ENGINEERING(SEE ATTACHED CITY
 SAMPLE FORM FOR SITE SPECIFIC DOOR)
 SIGNED AND SEALED BY THE ENGINEER AND
 BY THE DESIGNER OF RECORD.
 **NOTE: ENGINEER TO CLARIFY WHY FORM
 SUBMITTED SAYS THAT 2X BUCK DETAIL IS
 NOT STRUCTURAL.
 6-CLARIFY WHY PERMIT APPLICATION AND
 ENERGY CALCULATIONS HAVE DIFFERENT
 CONTRACTORS NAME.