2003-04-29 00:00:00BUILDING REVIEW CHECKLIST:
 1-REAR ELEVATION EXCEEDS THE MAXIMUM
 PERCENTAGE OF OPENINGS ALLOWED BY
 TABLE 600 FBC 2001. REVISE AS REQUIRED
 2-PROVIDE SOIL TEST REPORT.
 3-PAY IMPACT FEES BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 4-NEED RECORDED NOTICE OF COMMENCEMENT.
 5-STORM SHUTTERS: A)DRAWINGS NEED TO
 HAVE ENGINEER'S SEAL AND SIGNATURE AS
 REQUIRED BY DESIGNER ENGINEER ON NOTE
 #6 ON PAGE 1 OF 9.
 B)DRAWINGS DON'T MATCH THOSE REFERENCED
 ON SBCCI REPORT. SEE NUMBER OF DWGS
 AND LATEST REVISIONS.
 **NOTE: THERE IS AN UPDATED SBCCI REPORT
 #2229A. ALSO, GET MATCHING DRAWINGS.
 C)CHECK THE DESIGN PRESSURES AND MAX./
 MIN. PANEL SPAN SHOWN ON INSTALLATION
 SCHEDULE AND THOSE SHOWN ON ENGINEERED
 DRAWINGS AND REVISE SCHEDULE AS REQ'D.
 ALSO, CHECK ANCHOR SPACING.
  
 6-A)PROVIDE PRODUCT APPROVAL FOR FRENCH
 DOORS WITH SIDELITES AS SHOWN ON PLANS
 B)RESUBMIT PRODUCT APPROVAL FOR SINGLE
 HUNG WINDOWS WITH LEGIBLE DRAWINGS.
  
 7-REVISE SPECIFICATIONS FOR INSTALLATION
 OF METAL LATH AT PORCH CEILING. SEE
 ASTM C-1063 FOR SIZE OF FASTENER
 REQUIRED. NEED 1 3/4" PENETRATION TO
 HORIZONTAL MEMBER AND 1 3/4" STAPLES
 DON'T PROVIDE THIS REQUIREMENT. REVISE
 SPECIFICATIONS AS REQUIRED.
 8-PROVIDE COMPLETE DETAIL AND FASTENERS
 SPECIFICATIONS FOR INSTALLATION OF
 AIR HANDLER UNIT HANGING FROM TRUSSES.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 9-COMPLETE INFORMATION ON TOP OF THE
 ENERGY CALCULATIONS. EG: OWNER.