| 2003-04-29 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-REAR ELEVATION EXCEEDS THE MAXIMUM |
| | PERCENTAGE OF OPENINGS ALLOWED BY |
| | TABLE 600 FBC 2001. REVISE AS REQUIRED |
| | 2-PROVIDE SOIL TEST REPORT. |
| | 3-PAY IMPACT FEES BRING BACK STAMPED |
| | DRAWINGS AND PAID RECEIPT. |
| | 4-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 5-STORM SHUTTERS: A)DRAWINGS NEED TO |
| | HAVE ENGINEER'S SEAL AND SIGNATURE AS |
| | REQUIRED BY DESIGNER ENGINEER ON NOTE |
| | #6 ON PAGE 1 OF 9. |
| | B)DRAWINGS DON'T MATCH THOSE REFERENCED |
| | ON SBCCI REPORT. SEE NUMBER OF DWGS |
| | AND LATEST REVISIONS. |
| | **NOTE: THERE IS AN UPDATED SBCCI REPORT |
| | #2229A. ALSO, GET MATCHING DRAWINGS. |
| | C)CHECK THE DESIGN PRESSURES AND MAX./ |
| | MIN. PANEL SPAN SHOWN ON INSTALLATION |
| | SCHEDULE AND THOSE SHOWN ON ENGINEERED |
| | DRAWINGS AND REVISE SCHEDULE AS REQ'D. |
| | ALSO, CHECK ANCHOR SPACING. |
| | |
| | 6-A)PROVIDE PRODUCT APPROVAL FOR FRENCH |
| | DOORS WITH SIDELITES AS SHOWN ON PLANS |
| | B)RESUBMIT PRODUCT APPROVAL FOR SINGLE |
| | HUNG WINDOWS WITH LEGIBLE DRAWINGS. |
| | |
| | 7-REVISE SPECIFICATIONS FOR INSTALLATION |
| | OF METAL LATH AT PORCH CEILING. SEE |
| | ASTM C-1063 FOR SIZE OF FASTENER |
| | REQUIRED. NEED 1 3/4" PENETRATION TO |
| | HORIZONTAL MEMBER AND 1 3/4" STAPLES |
| | DON'T PROVIDE THIS REQUIREMENT. REVISE |
| | SPECIFICATIONS AS REQUIRED. |
| | 8-PROVIDE COMPLETE DETAIL AND FASTENERS |
| | SPECIFICATIONS FOR INSTALLATION OF |
| | AIR HANDLER UNIT HANGING FROM TRUSSES. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 9-COMPLETE INFORMATION ON TOP OF THE |
| | ENERGY CALCULATIONS. EG: OWNER. |