Plan Review Notes
Plan Review Notes For Permit 03031930
Permit Number 03031930
Review Stop P
Sequence Number 3
Notes
Date Text
2004-11-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS, NOR DOES IT REFLECT
 THE FLOOR PLAN.
 A) SHOWER NOT VENTED IN GUEST SUITE
 BATHROOM. 909.2.1
 B) MASTER BATH TUB TO BE TO THE LEFT OF
 THE LAV AS SHOWN ON THE FLOOR PLAN.
 SECTION 104.2.1
 C) EXTRA BATHROOM ON RISER DIAGRAM IS
 NOT SHOWN ON THE FLOOR PLAN. SECTION
 104.2.1
 D) 3" VENT THRU ROOF HAS NO FIXTURE ON
 THE STACK. EVERY DRY VENT CONNECTING TO
 A HORIZONTAL DRAIN SHALL CONNECT ABOVE
 THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE. SECTION 905.3
 E) 2" TO PRO VENT HAS NO FIXTURES ON
 THE BRANCH LINE. PLEASE CLARIFY. SECTION
 104.2.1
 F) THE WASH MACHINE AND LAUNDRY SINK
 ARE NOT SHOWN ON THE RISER DIAGRAM.
 SECTION 104.2.1
 2) A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL DRAWINGS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 FAC 61G1-16.004 & FS481.2055/481.219
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]