Plan Review Notes
Plan Review Notes For Permit 03031930
Permit Number 03031930
Review Stop E
Sequence Number 2
Notes
Date Text
2003-11-13 00:00:00DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE TWO FULL SETS OF PLANS
 FOR REVIEW.THERE IS ONLY ONE OF SHEETS
 A.5 AND A.6.ALSO HAVE THESE SHEETS
 SEALED, SIGNED AND DATED BY THE
 ARCHITECT PER FS 481 AND 16G1-16.001
 FAC THE ONES THAT WERE SUBMITTED WERE
 NOT SEALED.
  
 NOTE #2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG. AND NOTE #4
 RE: REMOVE THE EQUIPMENT GROUNDING
 CONDUCTOR FROM THE METER TO THE FIRST
 MEANS OF DISCONNECT,WERE NOT CORRECTED
 ON THE PLANS.THE EQ GND IS STILL ON
 THE RISER AND CREATES A PARALLEL PATH
 WITH THE NEUTRAL CONDUCTOR.PLEASE
 REMOVE FROM PLAN.THE BATH CIRCUIT IS
 STILL ON A 15 AMP BREAKER.
  
 ALSO THE SMALL APPLIANCE CIRCUITS THAT
 ARE REQUIRED BY 210.11(C)(1) WERE NOT
 ON THE SCHEDULE AND WERE NOT IN THE
 CALCULATIONS PER 220.16(A).PLEASE
 INCLUDE SAME ON PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718