| Plan Review Notes For Permit 03031930 |
| Permit Number |
03031930 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-11-13 00:00:00 | DENIED | | | ~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE TWO FULL SETS OF PLANS | | | FOR REVIEW.THERE IS ONLY ONE OF SHEETS | | | A.5 AND A.6.ALSO HAVE THESE SHEETS | | | SEALED, SIGNED AND DATED BY THE | | | ARCHITECT PER FS 481 AND 16G1-16.001 | | | FAC THE ONES THAT WERE SUBMITTED WERE | | | NOT SEALED. | | | | | | NOTE #2} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. AND NOTE #4 | | | RE: REMOVE THE EQUIPMENT GROUNDING | | | CONDUCTOR FROM THE METER TO THE FIRST | | | MEANS OF DISCONNECT,WERE NOT CORRECTED | | | ON THE PLANS.THE EQ GND IS STILL ON | | | THE RISER AND CREATES A PARALLEL PATH | | | WITH THE NEUTRAL CONDUCTOR.PLEASE | | | REMOVE FROM PLAN.THE BATH CIRCUIT IS | | | STILL ON A 15 AMP BREAKER. | | | | | | ALSO THE SMALL APPLIANCE CIRCUITS THAT | | | ARE REQUIRED BY 210.11(C)(1) WERE NOT | | | ON THE SCHEDULE AND WERE NOT IN THE | | | CALCULATIONS PER 220.16(A).PLEASE | | | INCLUDE SAME ON PLANS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|